Instruction manual

9
4.3 DCM check points, and board test points.
(The reference point for test point measurements can be circuit common at TB1- 1,7,8 or
10)
TP1: Field current; 10V = 100% (100% is the J1 selected value)
TP2: Armature voltage (7.7V = motor base voltage)
DCM A: 12VDC +5%
DCM B: 5VDC +5%
DCM C: 15VDC +5%
DCM D: -15VDC +5%
DCM E: Field current (scaled IFB, 2.37V = 100%)
DCM F: Armature over voltage fault (high = true)
DCM G: 20VDC +7%
DCM I: Scaled tach output (7v/1000RPM)
DCM J: Field current (10V = 100%)
DCM K: Field undercurrent fault (high = true)
DCM L: Scaled tach input
DCM M: Current reference (10v = Max current, 0v = Min current)
DCM N: Scaled armature volts (7.7v = 100% armature volts)
DCM O: Field economy (low = true)
DCM P: Crossover set point
DCM R: -20VDC + 7%
DCM S: Regulation trigger voltage (regulation loop error) sums with the phase
reference saw tooth voltage to create the trigger pulses
DCM T: Field weakening voltage (>10 v = Max field, <0v = Min field)