Instruction manual
Appendix 8. Instruction Manual for Compliance with UL/c-UL Standard
A8 - 8
U, V, W
Capacity [kW] 0.4, 0.75 1.5 2.2, 3.7 5.5 7.5 11.0 15.0
#14/60°C #10/60°C #10/60°C #8/60°C #8/60°C #4/60°C Wire Size (AWG)
/Temp Rating
Note 1
#14/75°C #14/75°C #12/75°C #10/75°C #8/75°C #4/75°C
5.5-S4 R5.5-4 R8-5 Crimping
Terminals Type
R2-4
R2-4
R5.5-5
R5.5-5
R8-5
L330T
459-23
YHT-8SCrimping Tools
Type
YHT-2210
YHT-2210
YHT-8S YPT-60
#14/60°C #11/60°C #10/60°C #8/60°C #8/60°C #4 /60°C Earth Wire Size
(AWG)
#14/75°C #14/75°C #10/75°C #10/75°C #8/75°C #4 /75°C
Capacity [kW] 18.5 22.0 26.0 30.0 37.0 45.0 55.0
#3/60°C #2/60°C #1/60°CWire Size (AWG)
/Temp Rating
Note 1
#4/75°C #3/75°C #2/75°C
#1/75°C #1/0/75°C
#2/0
75°C
#4/0
/75°C
22-S6
Crimping
Terminals Type
L330T
459-23
R38-8 R60-8 70-10 R100-10
Crimping Tools
Type
YPT-60
YET300
YF-1
YPT-150
#3/60°C #3/60°C Earth Wire Size
(AWG)
#4/75°C #3/75°C
#3/75°C #1/75°C #1/75°C
#3/0
/75°C
Note 1: 60°C: Polyvinyl chloride insulated wires (IV)
75°C: Grade heat-resistant polyvinyl chloride insulated wires (HIV)
Use copper wire only.
Above listed wire are for use in the electric cabinet on machine or equipment.