Instruction manual
Appendix 7. EMC Installation Guidelines
A7 - 8
Appendix 7-6 EMC countermeasure parts
Appendix 7-6-1 Shield clamp fitting
The effect can be enhanced by connecting the cable directly to the earthing plate. Install an earthing
plate near each panel's outlet (within 10cm), and press the cable against the earthing plate with the
clamp fitting. If the cables are thin, several can be bundled and clamped together. Securely earth the
earthing plate with the frame ground. Install directly on the cabinet or connect with an earthing wire.
Contact Mitsubishi if the earthing plate and clamp fitting set (AERSBAN- SET) is required.
Note 1) Screw hole for wiring to earthing plate in cabinet.
Note 2) The earthing plate thickness is 1.6mm.
A B C Enclosed fittings L
AERSBAN-DSET 100 86 30 Clamp fitting A × 2 Clamp fitting A 70
AERSBAN-ESET 70 56 – Clamp fitting B × 1
Clamp fitting B 45
CAUTION
The shield of the spindle detector cable is not connected to the "FG"(Earth). Do
not connect the cable shield to the earth by clamping the cable, etc.
View of clamp section
• Outline drawing