User Manual

59
Pump shutting down on
Pump Protection
Fault in protection sensor Replace or adjust sensor
Controller powers on and
off continuously
Voltage being applied to the
Inputs.
Excessive current being
drawn from the external
pressure sensor
Make sure that the Inputs are Voltage
Free
Check external sensor current 100mA
max.
Can’t tune the set point
above/Below a number
The set point must be
between the Cut In pressure
and the High Pressure limit
Adjust HP limit or Cut In pressure to allow
the Set point to move
Check Set Point 2 & 3 to make sure that
they are not above HP Limit or below Cut
In pressures
System Displays wont
initialise
Loading Data message
cycles continuously
System needs to be
initialised.
Press the “Commissioning Button” on the
PCB whilst powering up the system to
initialise the program
System Pressure not
displaying
Analogue circuits not
functional
There are 2 LED’s located on the front
top right of the PCB. One is for Power
which should be flashing – the other is for
indication that the analogue circuit is
operational. Solid light means OK- No
light means inoperative.
PROBLEM CAUSE SOLUTION
INSTALLATION NOTES
Here are some “GOLDEN RULES” in site installation that should be followed.
Site Installation
Select the site most shaded and out of direct sunlight. Heat is a VSD killer.
Allow the airow from the fans to be unimpeded.
Always connect the motor earth directly to the earth within the VSD.
Inputs
Connect the shield to EARTH and one end only.
Never apply voltage to the Inputs.
Take care in running inputs for long distances.
The inputs use a 24VDC signal as the carrier voltage - use compliant sensors.
Outputs
5 amp maximum switching load.
Check the programming on each output before trying to troubleshoot.
Start-up
CHECK ROTATION CHECK ROTATION CHECK ROTATION CHECK ROTATION
All these items are site related