User Manual
36
Flow Type
The “Flow Type” setting allows the user to select how the ow rate is determined.
Options are Calculated, Scaled AnInp2 or Digital Pulse.
• “Calculated” uses the ow rate setting “Pump Flow Rate” in the settings menus to calculate the current
Flow Rate.
• “Scaled AnInp2” uses an analogue sensor (ether current-loop or variable voltage ) to determine the
current Flow Rate.
• Digital Pulse uses a compatible digital output ow meter to determine the current Flow Rate.
Manual Run
Serial Comms selects how the onboard RS-485 serial port is used.
• Output Cont Data options is a data logging option that allows the pump station
to be remotely or locally logged.
• Modbus Protocol allows modbus compatible interfaces to monitor and adjust values during operation.
Duty
If a pump is dened as Duty, then the relevant pump will be available for operation.
The number of pumps visible in these screens is determined by the “number of pumps” screen within
the CONFIGURE menu.
If pump 1 is dened as Jockey the “JOCKEY PUMP” menu will become visible.
Flow Type
Calculated
Manual Run
Input or P_But’n
Pump 1
Duty
Pump 1 selection Duty, Jockey Duty
Pump 2 selection Duty Duty
PUMP DEFINITIONS
JOCKEY PUMP
Jockey Pump Mode selection DOL, Main VSD, Separate VSD Main VSD
JP Cut In Pressure
% of JP
Setpoint
0 - 9999 250
JP Cut Out Pres Unitless 0 - 9999 300
JP Set Point Unitless 0 - 9999 300
JP Flow Rate /Sec 0 - 9999 50
JP Response Rate % 0.1 - 100.0 3.0
JP Acceleration %/second 1 - 100 20
JP Standby Test selection Off,Boost,Flow Switch, Flow Rate Boost
JP Standby Boost
% of JP
Setpoint
5 - 250 5
JP Stdby FlowMin /Sec 0 - 250 5
JP Run On Time seconds 0 - 999 1
JP Restart Delay seconds 0 - 999 0
JP Use Main SP selection Yes, No No