PUMP DATA LOG
NOTE: The FAULT HISTORY menu is cleared when the system is rst powered up.
If there is a problem with the clock or the clock hasn’t been initialised correctly then “RTC ERROR” will appear
along with the fault. See “Set Time and Date” in the CONFIGURE menu for more details.
“Pump 1 - 2 Shutdown” signies that the corresponding “Pump protect 1-6” input has been activated for the
period of the input delay time.
A HIGH TEMPERATURE fault is recorded when the temperature rises above 60 degrees C. This fault will
continue to be updated if the temperature continues to
rise along with the time and date that the highest temperature was recorded.
This fault stops being updated when the temperature drops below 55 degrees C.
After this a new fault will appear if the temperature rises above 60 degrees C.
“Auto Reboot” denotes that the Speedman has automatically restarted due to an internal reset, whereas
“Power Failure” records that the Speedman has recovered from a power supply problem.
The FAULT HISTORY menu is always accessible (no access code is required)
Flow Total
The Totalised Flow is displayed. It is calculated from the ow rate input and can be
derived from a ow meter or the calculated “Flow Rate” gure set in the Pump Flow
Rate Screen in SETTINGS.
If the Speedman uses Flow Rate/Sec to calculate “Total Flow”, the value is based on the Average Flow input
into the system. The accuracy is dependent on the average ow information and is most often in the order of
accuracy of ±5%. Site variations such as suction pressure can affect the accuracy of this gure. The FLOW
TOTAL is updated every 1 minute and can be reset by pressing ENTER.
Average Flow Rate
The Average ow is calculated over the period since the last reset. The ow units are
derived either from a calculated ow or the input from a ow meter.
To reset press ENTER.
Flow Total
XXXXXXX
Average Flow Rate
XXXX /Sec
F1 Hi Temp 69C
01/04/08 11:51
Flow Total Unitless 0 - 9999999 display
Average Flow Rate /Sec 0 - 9999 display
Average Pressure Unitless 0 - 9999 display
Highest Pressure Unitless 0 – 9999 display
Hours Run 1 hours 0 - 65535 display
Hours Run 2 hours 0 - 65535 display
Pump Starts 1 number 0 - 65535 display
Pump Starts 2 number 0 - 65535 display
Pump Starts Last Hr number 0 - 65535 display
Analogue Input 1 % 0.00 - 100.00 display
Analogue Input 2 % 0.00 - 100.00 display
Analogue Output 1 % 0.00 - 100.00 display
Analogue Output 2 % 0.00 - 100.00 display
Digital Input State M 1 - 8 X for Active display
Digital Output State 1 - 2 X for Active display
PID Error % 0.00 - 100.00 display
Curr & max retry number 0-20 0-20 display
Temperature degrees C 0 - 999 display
Modbus monitor Rx, Tx, Err 0-9999 display