* All of these menus are not visible unless Pump 1 is congured to be a Jockey Pump
1 Menu only visible if the JP Standby Test mode is set to the matching function.
2 Appears when Jockey Pump Mode is set to DOL
3 When Jockey Pump Mode is set to DOL this optional has no function and will not be visible
4 Not visible when JP Use Main SP) Set Point) is set to YES
Sub Menu Units Range Defaults
JOCKEY PUMP
* Jockey Pump Mode selection
Main VFD, Separate
VFD, DOL
Main VFD
* JP Cut In Pressure % of JP Setpoint 0 - 9999 83.3
2 JP Cut Out Pres Unitless 0 - 9999 300
* 3 JP Set Point Unitless 0 - 9999 300
* JP Flow Rate /Sec 0 - 9999 50
* 3 JP Response Rate % 0.1 - 100.0 3.0
* JP Acceleration %/second 1 - 100 20
* 3 JP Standby Test selection
Off,Boost,Flow Switch,
Flow Rate
Boost
* 1 3 JP Standby Boost % of JP Setpoint 5 - 250 6.6
* 1 3 JP Stdby FlowMin /Sec 0 - 250 5
* JP Run On Time seconds 0 - 999 1
* JP Restart Delay seconds 0 - 999 0
* 3 JP Use Main SP selection Yes, No No
* 3 JP Min Frequency % 0.0 - 100.0 10
* 3 JP ErrorCorr’t (I seconds Off, 0.1- 100.0 15
* 3 JP OverShtElim (D % Off, 0.01 - 50.00 4
Sub Menu
Units
Range
Defaults
TIME OF DAY SP
Set Point 2 Time time Disabled, 00:00 - 23:59 Disabled
Set Point 3 Time time Disabled, 00:00 - 23:59 Disabled
Set Point 4 Time time Disabled, 00:00 - 23:59 Disabled
Set Point 5 Time time Disabled, 00:00 - 23:59 Disabled
Set Point 6 Time time Disabled, 00:00 - 23:59 Disabled
Set Point 7 Time time Disabled, 00:00 - 23:59 Disabled
Set Point 8 Time time Disabled, 00:00 - 23:59 Disabled