Sub Menu Units Range Defaults
CONFIGURE
Operating Mode selection Pressure, Level, Pressure
*1 Level Mode selection
Std An:Tank Fill, Std An:TankEmpty, Rev
An:Tank Fill, Rev An:TankEmpty
Std An:Tank
Number of pumps number 1 – 2 1
Min Freq Mode selection Fixed, Calculated Fixed
Press Decimal number 0 – 3 0
Flow Decimal number 0 – 3 0
*2 Transducer Zero Unitless 0 - 9999 *3
*2 Adjust Pressure Unitless 0 - 10000 *3
Averaging number Disabled, 1 - 50 5
*4 Flow Meter Zero /Sec 0 - 9999 0
*4 Adjust Flow /Sec 0 - 10000 1000
*9 Backup Pres Zero Unitless 0 - 9999 0
*9 Adjust Backup Pr Unitless 0 - 9999 0
*5 Scale An output 2 number 100 – 10000 1000
JP Fallback selection On. Off Off
*6 Standby Test selection Boost, Flow Switch, Flow Rate, Off Boost
*8 Fallback Test selection Flow Switch, Flow Rate Flow Rate
Set Time/Date selection 00:00 2000 Jan 1 -23:59 2099 Dec 31. 00:00 2000 Jan 1
Operating System selection Lead VSD Lag Lead VFD Lag
*6 Friction Loss Calc selection Linear, Exponential Linear
*7 Access Code number Off, 0 - 250 21
Serial Comms selection Output Cont Data, Modbus Protocol Modbus Protocol
Modbus Address number 1 - 31 1
Flow Sensing selection Calculated, Scaled AnInp2, Digital Pulse Calculated
Manual Run selection Input or P_But’n, Input Only Input or P_But’n
* These menus are related to other settings. They are not visible unless related settings are enabled
*1 Only shown if Operating Mode is set to Level.
*2 These menus show a value that is decoupled from the value that you are changing. Thus one press up
and one press down may not corresponded to +1 or -1 change in value.
*3 These settings are by default setup for a 4-20ma sensor with the range of 0-25bar (2500 kpa).
However it is still highly recommended that you calibrate the Speedman for your sensor.
*4 These menus are only visible when one of the Analogue inputs is congured as a ow meter.
*5 Menu hidden when Analogue output 2 is congured as VSD speed.
*6 Menu hidden when in level mode.
*7 The Access Code allows you to change the access code and also determine which features require
you to enter an access code.
*8 Menu hidden unless “JP Fallback” is set to “On” in the CONFIGURE Menu.
*9 Menu hidden unless “Analogue Input 2” is set to “Backup Pressure” in the CONFIGURE Menu.
*
Whether or not these options are shown depend on how many pumps are congured in the Conguration Menu.
Sub Menu Units Range Defaults
PUMP DEFINITIONS
Pump 1 selection Duty,Jockey Duty
* Pump 2 selection Duty Duty