Sub Menu Units Range Defaults
TUNING
*1 Minimum Frequency % 0.0 - 100.0 45.0
*1 Shutoff Head Unitless 0 - 9999 1924
*2 Response Rate (P % 0.1 - 100.0 2.0
Acceleration %/second 1 - 100 20
Hi Press Restarts number Off, 1 - 250 Off
Standby Boost % of Setpoint 10 - 250 20
*6 Standby Flow Min /Sec 0 - 9999 200
*5 Fallback FlowMin Unitless /Sec 1 - 9999 200
*2 Error Correction (I seconds
Off,
0.1 - 100.0
3.0
*2 Overshoot Elimination (D %
Off,
0.1 - 50.00
15.0
*4 RR(P) EC(I) OE(D) Numbers x 3 -1000, 1000 Display only
* These menus are related to other settings. They are not visible unless related settings are enabled
*1 Either Minimum Frequency or Shutoff Head will be displayed depending on what the required method
for obtaining the point at which the pump will not contribute ow. This will either be “Calculated” via the
“Shutoff Head” or “Fixed” via a “Minimum frequency” and is set in the Congure Menu.
*2 The effect of changing values in these menus are instantaneous. The system will respond as these
values are changed. These menus also show the current pressure to the right in brackets to assist
tuning.
*4 These three menu items are displayed on single screen.
*5 Fallback FlowMin is only displayed if “JP Fallback” is set to “On” in the CONFIGURE Menu.
*6 Standby FlowMin is only displayed if “JP Fallback” is set to “Off” and the “Standby Test” is set to “Flow
Rate” in the CONFIGURE Menu.