TROUBLESHOOTING
TORRIUM
®
a) PUMP HAS STOPPED OR MOTOR RUNS FOR SHORT PERIOD
ONLY WHEN SWITCHED ON OR PRIME BUTTON PUSHED, BUT
DOES NOT PUMP - STATUS INDICATOR LIGHT ILLUMINATED RED
FLASHING ONCE PER SEQUENCE
1. Suction line and pump body not lled with water.
2. Air leaks in suction lines or suction pipe not under water.
3. Air trapped in suction lines (also possible with ooded suction due to
uneven rise in piping; eliminate humps and hollows).
4. No water at source or water level too low.
5. Valve on suction lines closed. Open valve & pump will restart
automatically or press “Prime” button.
b) PUMP SWITCHES ON AND OFF FREQUENTLY (CYCLING)
1. Cycling may occasionally be caused by oat valves lling tanks - see
“Cistern Fill Mode”.
2. Leaking taps, oat valves etc. check plumbing.
3. Leaking check valve/foot valve.
4. Discharge plumbing has been connected to the priming port.
c) MOTOR DOESN’T START WHEN SWITCHED ON - LOW PRESSURE
INDICATOR LIGHT NOT ILLUMINATED
1. Power not connected or no power available from supply outlet.
d) MOTOR STOPS - STATUS INDICATOR LIGHT IS ILLUMINATED RED,
FLASHING TWICE PER SEQUENCE
1. Motor ”over temperature” cut-out tripped. Consult Davey dealer.
2. Motor not free to turn - e.g. a jammed impeller. Consult Davey
dealer.
3. Prime button has been held in for too long. Release prime button
and switch off power for 1 minute to allow unit to reset.
e) PUMP WILL NOT STOP
1. Water leaks on discharge side of pump.
WARNING: Automatic reset thermal overloads may allow the pump to restart
without warning. Always disconnect the pump motor from the electrical supply
before maintenance or repairs.
WARNING: When servicing or attending pump and/or controllers, always
ensure power is switched off and lead unplugged. Electrical connections
should be serviced only by qualied persons.