Instruction manual

Strata DK424i
Primary/Reserve Power Cabinet Hardware
Strata DK General Description 6/00 33
BBTC1A-2.0M
A two-meter battery cable used to connect reserve power batteries to the BBDB battery
distribution box. One reserve power cable is required in a three or four cabinet system and two
cables are required for five cabinet systems (wall or floor mount). The cable connects DK424i
BBDB box directly to the battery terminals.
BCCB120 or
BCCB240
DK424i conduit connection box is installed in the bottom cabinet, side panel. It is used to hardwire
Primary AC power and reserve battery power connections through conduit. These boxes are
required by UL for three or more floor mounted cabinets. Conduit boxes are not required for wall
mounted systems with any number of cabinets or floor mounted system with one or two cabinets.
They can be used as an option on any system.
The BCCB120 is required when connecting AC120VAC as the primary power source and the
BCCB240 is required when connecting AC208VAC or AC240VAC as the primary power source.
BCCB conduit boxes must be field installed by a certified electrician.
BFIF
Floor mount fixture kit is required when floor mounting DK424i cabinets.
Provides two metal stands for mounting any number of DK424i cabinets on the floor. Three pairs
or wall brackets (RWBF) are supplied with BFIF to use when mounting three or more DK424i
cabinets on floor. The wall brackets are needed to secure floor-mounted systems to the wall for
safety purposes.
Table 27 Power Cabinet Hardware (continued)
Option Description