Instructions
UM-0085-B09  DT80 Range User Manual  Page 62 
RG 
Loading an Existing Job 
The DT80 can also read job text from a file stored in its internal file system and automatically enter it. This job will then 
become the current active job, replacing whatever was previously the current active job. 
A new job may be loaded when: 
•  the RUNJOB"jobname" command is issued. This will read the job from the file 
B:\JOBS\jobname\PROGRAM.DXC. 
•  the DT80 is reset. By default, the previously active job will be loaded (See Startup Job (P64)) 
•  A USB memory device is inserted. If a file A:\ONINSERT.DXC or A:\serialnum\ONINSERT.DXC is 
present then any commands therein will be executed. These may include a job definition, in which case the job 
will become the current active job. (See ONINSERT Job (P64)) 
Job Structure 
A typical DT80 job is shown below (the line numbers are for reference only and are not part of the job): 
1 
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19 
BEGIN"Boiler01" 
' No. 1 Boiler monitoring job for DT80 03
-Dec-2005 
/n/u/S/e
P22=44
Y10=4.5,0.312"kPa"
S1=0,50,0,100"L/m"
1DSO=0 
' Enable sensor power relay 
RS5S
RB1M 
2..3TT("Temp") 
RC(DATA:NOV:365D)15M 1V(Y10,AV) 4#L(S1,AV)
RK10S
ALARM1(1V(Y10)>2.25)3DSO 
ALARM1(4TT>110.0)3DSO,1CV"Over Temp ?"{RB5S}" 
LOGON
END 
Note the following salient points: 
•  Line 1 – the 
BEGIN command tells the DT80 to clear the current job and prepare to receive a new one. 
•  Line 2 – anything following a single quote character (up to the end of the line) is considered a comment and is 
ignored. Blank lines are also ignored. 
•  Line 3-7 – the first part of a job normally consists of commands to set switches and parameters, define 
polynomials and spans, and evaluate any immediate channels. 
•  Line 8 – this line sets the scan rate for the statistical sub-schedule. All channels which include a statistical 
channel option, i.e. 
1V(AV) and 3#L(AV), will therefore be scanned every 5 seconds. The measured values 
will not be logged or returned; they will only be used for accumulating the average values. 
•  Line 10 – defines the B schedule (measure two thermocouples once per minute). 
•  Line 12 – defines the C schedule (report pressure and flow rate values, averaged over a 15 minute period. Note 
the use of a polynomial (
Y10) to convert the measured voltage in mV to pressure in kPa. Similarly, a span is 
used to convert a current loop % value to a flow rate in l/m.) 
•  Line 14-16 – define the K schedule (every 10s check pressure and temperature against limits. If pressure 
exceeds 2.25kPa then set digital output 3 to LOW (active); if temperature exceeds 110°C then set digital output 
3 to LOW, set 1CV=1, output and log an "Over Temp" alarm string, and change the scan rate of schedule B to 
5s.) 
•  Line 18 – enables logging for all schedules (by default logging is disabled) 
•  Line 19 – marks the end of the job; all schedules will now be activated. 