Instructions
UM-0085-B09  DT80 Range User Manual  Page 58 
RG 
  Insufficient Statistical Samples 
If no statistical data has been scanned before being reported, then the reported data value will be set to NotYetSet. This 
will also occur if insufficient samples have been taken – for example, the standard deviation (SD) option requires at least 
two samples to be able to return a value. 
This condition may occur when 
•  the statistical sub-schedule is event-triggered 
•  the statistical sub-schedule has been halted 
•  a statistical sub-schedule scan interval is longer than its statistical report scan interval 
When using statistical channel options you need to ensure that the statistical and report schedule triggers are selected 
such that sufficient statistical samples are taken between each execution of the report schedule. 
  Example — Statistical Report Schedule 
The command 
  RS10S RA1H 1TT 2TT(AV)(MX) 
sets the statistical sub-schedule’s scan rate to 10 seconds (
RS10S). 
The main report schedule returns three temperature readings: a spot reading of channel 1 each hour (
RA1H 1TT), and 
the average and maximum over the hour from 10-second samplings of channel 2. 
Working with Schedules 
Entering Schedules into the DT80 (BEGIN–END) 
Report schedules must be entered into (that is, sent to) the DT80 as a group. Since the schedules and processes that 
comprise a job or program often extend over more than one line, you normally enclose them between the keywords 
BEGIN and END to designate the beginning and end of the group. Here’s an example: 
BEGIN"walrus" 
   1DSO=1 
   3CV(W)=2 
   RA10S 
    4TT("Oven Temp") 
    5TT("Flue Temp") 
   RB1S  
    2C("Water Flow") 
END 
A group of schedules such as this is called a job. In the above example, the job has been named "walrus" and 
comprises two report schedules, 
RA (which measures two thermocouples every 10 seconds) and RB (which measures a 
counter once a second). Note also the two "immediate" channels (
1DSO and 3CV) which are not part of any schedule. 
These are executed once only, when the job is entered. 
For more details on how jobs are entered and processed, see Jobs (P61). 
Triggering and Schedule Order 
When different schedules are due to trigger at the same time, the schedules execute in the order of RA, RB,…RK, RX. 
When there are statistical channels in a schedule and the statistical sub-schedule is due at the same time as the report 
schedule, the statistical sub-schedule runs prior to the report schedules. You cannot change this order. Channels within 
schedules are sampled in the order of entry (left to right). 
For example, consider the job: 
BEGIN"cupcake" 
 RB2S 3V 
 RA5S 2V(AV)(SD) 1V 
 RS1S 
END 