Instructions
UM-0085-B09  DT80 Range User Manual  Page 60 
RG 
For example, if you enter 
RA1+E 1V HB SATTN 4CV=4CV+1 
you might expect that when the schedule was triggered (by a positive going edge on digital input 1) it would measure a 
voltage (1V), halt schedule B (HB), switch on the Attn LED (SATTN) and increment a channel variable (4CV=4CV+1). 
In fact, the HB and SATTN will execute once only, when the job is entered. The 1V and 4CV=4CV+1 are channel 
definitions, so they will execute each time schedule A is triggered. 
To execute commands within a schedule, the 
DO construct can be used. This is actually a special case of the ALARM 
statement (see Alarms (P82)) – one where the condition is always true. The syntax is the same as 
ALARM except that 
there is no test condition. 
So if the above job was rewritten as: 
RA1+E 1V DO{HB SATTN} 4CV=4CV+1 
then the following actions would be performed each time schedule A is triggered: 
•  Channel 1V is measured, then channel variable 4CV is incremented 
•  The commands 
HB and SATTN are queued for execution. They will be actioned "as soon as possible" – once 
all schedules that are currently due have completed, and any previously queued commands have been 
executed. 
Note: it is not possible to interleave the execution of commands and channels within a schedule. Channels are always performed first; 
commands are executed a short time later. 
Commands can also be executed conditionally, using the IF construct, e.g. 
RA1M IF(1CV>3.57){XB} 
will test the value of 1CV once a minute. If it exceeds 3.57 then schedule B will be triggered. 
For more details on 
ALARM/ IF/ DO syntax and usage, see Alarms (P82). 
Time Triggers — Synchronizing to Midnight 
Time triggers for report schedules function in two different ways depending on the setting of the synchronize-to-midnight 
switch (
/s or /S, see (P262)). 
  Synchronize-To-Midnight Switch Enabled 
If the synchronize-to-midnight switch is enabled (/S, the DT80’s default), the intervals of all schedules with time triggers 
are synchronized to the previous midnight. 
When a time-triggered schedule is entered, the schedules first run on the next multiple of the interval since last midnight, 
and subsequently run on every multiple of the interval thereafter. 
If the interval is not an even multiple of 24 hours, the DT80 inserts a short interval between the last run of the schedule 
prior to midnight and the next run of the schedule at midnight. 
For example, if you send the schedule 
RA10H 
to the DT80 at 06:00:00, it first runs at 10:00:00 (4 hours since entry, but 10 hours since midnight) and then at 20:00:00 
that day; then at 00:00:00, 10:00:00 and 20:00:00 the next day; and so on. 
If you enter an interval longer than 24 hours then the interval is rounded down to the nearest multiple of 24 hours. So if 
the schedule 
  RA50H 
was entered at 09:00 Monday morning then the schedule will first run at 00:00 Wednesday morning, then every 48 hours 
thereafter. 
  Synchronize-To-Midnight Switch Disabled 
If the synchronize-to-midnight switch is disabled (/s), the schedules run at intervals relative to the time that the 
schedule is entered. For example, if the same 
RA10H schedule is sent to the DT80 at 09:30:00, it first runs at 19:30:00 
that day; then at 05:30:00 and 15:30:00 on the next day; at 01:30:00 and 11:30:00 on the following day; and so on. That 
is, every 10 hours of elapsed time. 
Note that the base time (the time at which the specified schedule interval begins) is reset whenever: 
•  the schedule rate is changed, or 
•  the schedule is restarted (using the 
G command), or 
•  the system time is changed (using the 
D=, T= or DT commands). 