UM-0085-B09  DT80 Range User Manual  Page 264 
RG 
Profile Settings 
The DT80 profile is a group of named settings which control aspects of the logger's operation. Unlike parameters and 
switches, profile settings are "permanent", in that they are not cleared by a soft or hard reset (INIT and HRESET 
commands respectively, see 
Resetting the DT80 (P273)) 
Structure 
The DT80's profile settings are divided into a number of sections, each of which deals with a particular area, e.g. host 
port, modem, Modbus server, etc. Each section is identified by name, e.g. "HOST_PORT". 
Each section then contains a number of keys (settings). Each key has a name (e.g. "BPS") and a value (e.g. "57600"). 
Depending on the key, the value may be a numeric, boolean (yes/ no) or string value. 
The value of any of the defined keys can be viewed of changed using the 
PROFILE command. 
The PROFILE Command 
The PROFILE command syntax is as follows: 
Command 
Description 
PROFILE 
return current settings for all profile keys 
PROFILE section 
return current settings for all profile keys in section 
PROFILE section key 
return current value of specified profile key 
PROFILE section key= 
set specified profile key to default value 
PROFILE section= 
set all keys in section to default value
PROFILE section key=keystring 
set specified profile key to keystring. Enclose in quotes, i.e. 
"
keystring
"
 if the 
string contains spaces or control characters 
  Displaying Profile Settings 
The following command will display all profile values in the HOST_PORT section: 
  PROFILE HOST_PORT 
[HOST_PORT] 
   BPS = 57600 
   DATA_BITS = 8 
   STOP_BITS = 1 
   PARITY = NONE 
   *FLOW = HARDWARE 
   FUNCTION = COMMAND 
When profile values are returned, an asterisk (*) before a key name indicates that the key has been changed from its 
factory default value. In the above example, to return the 
FLOW key to its default setting you would use: 
  PROFILE HOST_PORT FLOW= 
  Setting Profile Keys 
The following command will change the default host baud rate to 115200 bps: 
PROFILE HOST_PORT BPS=115200 
Profile setting changes generally take effect immediately. So in this case, if the active command port was the host RS232 
port then all subsequent commands would need to be sent at 115200 bps. 
The DT80 supports the following profile keys: 
Section Name 
Key Name 
Legal Values 
Factory Default 
Comment 
USER  SITE 
string 
Site name to display on LCD instead of 
job name 
HOST_PORT 
(not present on 
DT8xM models) 
BPS 
300, 600, 1200, 
2400, 4800, 9600, 
19200, 38400, 
57600, 115200 
57600 
Serial parameters for Host RS-232 port 
See Configuring the Host RS-232 
Port (P195) 
DATA_BITS 
7, 8 
8 
STOP_BITS 
1, 2 
1 
PARITY 
NONE, EVEN, ODD 
NONE 
FLOW 
HARDWARE, 
SOFTWARE, NONE 
SOFTWARE 
FUNCTION 
COMMAND, PPP, 
SERIAL, MODBUS, 
MODBUS_MASTER, 
DISABLE 
COMMAND 
Host port function: command/PPP 
interface, PPP interface, serial channel 
or Modbus 