Instructions
UM-0085-B09  DT80 Range User Manual  Page 234 
RG 
Alternatively, if a DHCP server was available on the network then you could simply use: 
PROFILE ETHERNET IP_ADDRESS=AUTO 
By default, the above command is assigned to one of the DT80's user defined functions, accessible from the front panel; 
see User Defined Functions (P120). This makes it easy to enable Ethernet on a new logger without having to connect to 
it. 
Setting DNS Server address 
To set the DNS server address use 
  PROFILE NETWORK DNS_SERVER_1=192.168.42.4 
  PROFILE NETWORK DNS_SERVER_2=192.168.42.5 
The first setting is for the primary DNS server; the second is for an optional alternative server, which will only be used if 
the primary server is offline. 
These settings will be ignored if valid DNS server address(es) were obtained from the DHCP server. 
Ethernet Email 
To send an email, an Internet-connected computer needs to send the message to an SMTP server (Simple Mail 
transport Protocol). This server, and its brethren around the world, will then take care of delivering the message to the 
specified email address. 
Thus in order for the DT80 to be able to send data or alarm messages via email, it will need to know the name of a 
suitable SMTP server. This may be a corporate email server on the local LAN, or it may be a mail service provided by 
your ISP, or it may be a third-party public SMTP server on the Internet (both free and paid email services are available). 
The DT80 only supports SMTP servers that: 
•  support LOGIN authentication 
•  do not require SSL (Secure Sockets Layer) encryption 
Note: gmail SMTP service aspmx.l.gmail.com may be used with some limitation on destination address since it may get filtered by 
destination server. 
Your email service provider will supply you with the SMTP server name, a username and a password, which you will 
need to enter into the DT80's profile, as follows: 
PROFILE ETHERNET_SESSION SMTP_SERVER=server name 
PROFILE ETHERNET_SESSION SMTP_ACCOUNT=email account name 
PROFILE ETHERNET_SESSION SMTP_PASSWORD=password 
You also need to specify the sender name and email address that the DT80 will use when sending email. For example: 
  PROFILE ETHERNET_SESSION SENDER_NAME="Benjamin Bunny" 
  PROFILE ETHERNET_SESSION RETURN_ADDRESS=bb@firtree.net 
If SENDER_NAME is not set then the DT80 model and serial number is used, e.g. "DT82EM-3 096605". 
The RETURN_ADDRESS profile should be set to the email address associated with your account. In the event that an 
email sent by the logger is unable to be delivered, a "bounce" error message will normally be sent to this address. 
In dEX, email settings are configured using the Ethernet email configuration page: 
Figure 92: Email configuration page 
In the above screen shot, the logger has been set up to use the (fictitious) third party email provider yourdomain.com. 
The server name, as specified by the provider, is smtp.yourdomain.com. The account name (user) and password have 
also been entered. 
Email sent by this logger will appear to come from "Turbine 12", with email address of YourLogger@yourdomain.com. 