Instructions
UM-0085-B09  DT80 Range User Manual  Page 195 
RG 
Host RS-232 Port 
Not applicable to DT82EM/ 80LM/ 85LM 
The DT80 has a 9-pin male connector for RS 232 serial communication to a computer or modem. The port is configured 
as a DTE (Data Terminal Equipment) device, and the pinout is the same as that used on a PC. See RS-232 (P392) for 
more details. 
Configuring the Host RS-232 Port 
There are three parameters that need to be set for any RS232 port, and the DT80's port is no exception: 
•  baud rate (data transfer rate in bits per second) DT80 default is 57600. 
•  serial framing format (number of data bits, parity type, number of stop bits) DT80 default is "N,8,1" – no parity, 8 
data bits, 1 stop bit. 
•  flow control (mechanism for one computer to tell the other to stop sending) DT80 default is software flow control 
(special characters are used to signal "stop" and "go"). 
It is essential that both ends of an RS232 link be configured identically – same baud rate, framing and flow control. 
A fourth parameter that needs to be set for the DT80 host port is the port function, which specifies the protocol used by 
the port – command, PPP, Modbus or generic serial. 
PROFILE Settings 
To view the current host port settings use the following command: 
  PROFILE HOST_PORT 
  [HOST_PORT] 
   BPS = 57600 
   DATA_BITS = 8 
   STOP_BITS = 1 
   PARITY = NONE 
   *FLOW = HARDWARE 
   FUNCTION = COMMAND 
which lists the current baud rate, framing format, flow control and port function. An asterisk indicates a non-default 
setting. See Profile Settings (P264)) for more details. 
If required, these settings can be changed using individual 
PROFILE commands, i.e.: 
PROFILE HOST_PORT key=value 
The following keys are defined: 
Key 
Value 
Default 
BPS 
baud rate. Use 
300
, 
600
, 
1200
, 
2400
, 
4800
, 
9600
, 
19200
, 
38400
, 
57600
, or 
115200
.  
57600 
DATA_BITS 
can be 7 or 8 
8 
STOP_BITS 
can be 
1 
or
 2 
1 
PARITY 
can be N (none), O (odd) or E (even) 
N 
FLOW 
NONE (no flow control)  
SOFTWARE (XON/XOFF) 
HARDWARE (RTS/CTS) 
SOFTWARE 
FUNCTION 
port function (see below) 
COMMAND 
For example, the following commands would configure the host port for serial connection to a Modbus client (e.g. a 
SCADA system), using the "standard" Modbus settings (19200 baud, 8 data bits, 1 stop bit, even parity, no flow control): 
PROFILE HOST_PORT BPS=19200 
  PROFILE HOST_PORT PARITY=EVEN 
  PROFILE HOST_PORT FLOW=NONE 
  PROFILE HOST_PORT FUNCTION=MODBUS 
Note1: These settings, as with all profile settings, will temporarily revert to default settings in the event of a "triple push" reset, see Safe 
Mode
 (P274)). 
Note2: Do not use software flow control (SWFC) if the port is using a binary (non-ASCII) protocol, such as Modbus or PPP or some 
serial sensor protocols. This is because flow control characters (XON/ XOFF) may legitimately appear in binary data, and if they do then 
they will be stripped out. This will cause data errors. 