Instructions
UM-0085-B09  DT80 Range User Manual  Page 131 
RG 
  Scaling 
The Scaling tab is where you define either a simple scaling factor (channel factor), or a span or polynomial. Selecting 
"Spans and Polynomials" will bring up a list of defined spans and polynomials on the left hand side. Clicking on an entry 
will show its details in the area on the right. 
Figure 27: Defining a polynomial 
Initially, no spans or polynomials will be defined. To add one, click the Add button, select Span or Polynomial, then 
enter the required coefficients. In the above screen shot, the following polynomial has been defined: 
  22.5 + 1.236x – 0.000275x2 
Note: span and polynomial definitions are shared between channels. If you now define a new channel, all previously entered spans and 
polynomials will be available for selection. This means that if you select an already defined polynomial and then edit it (change the 
coefficient values) then you may be affecting other channels. A warning is displayed when an existing span/polynomial is selected to 
remind you of this. 
  Statistics 
The Statistics tab is used to define additional statistical report values for the selected channel. 
Figure 28: Defining additional statistical report values 
For each row that is ticked, an additional measurement value will be calculated and reported. So in the above example a 
total of four values will be logged: the original measurement, plus the average, minimum and maximum values calculated 
over the period since the time the enclosing schedule was executed. 
If any statistical values are defined for a channel, the channel will then be sampled at the statistical schedule rate, rather 
than the rate of the channel's own schedule. It will, however, still be logged
 at its own schedule's rate.The statistical 
schedule rate is a global setting, which is set by clicking on the top level "logger" entry in the tree view. 