UM-0085-B09  DT80 Range User Manual  Page 399 
RG 
  Error Number – Description 
•  Cause/Action 
Error Category 
Syntax  Operation  Memory  Reading  Hardware 
  E105 – Invalid PROFILE section/key name 
•  Check spelling of section and key name in PROFILE 
command 
 
  E106 – Invalid PROFILE value 
•  Check that value being set in PROFILE command is 
valid 
 
  E107 – Counter is already used as a trigger 
•  The specified counter is already used as a schedule 
trigger and cannot be used again. 
 
  E109 – File IO error: detailed description 
•  An error occurred while reading or writing to a file on 
one of the drives (A: or B:). The detailed description will 
contain exact details of the error type. For example, a 
write-protected file cannot be written to. 
 
  E110 – Error accessing storefile: detailed 
  description 
•  An error occurred while reading or writing to a storefile 
containing logged data. The file may be corrupted. 
 
  E112 – Parameter/option conflict 
•  The specified combination of command parameters or 
channel options are not valid 
 
  E113 – Schedule option error 
•  Invalid schedule option specified 
 
  E114 – Command parameter error 
•  Invalid parameter specified for a command 
 
  E115 – Serial sensor control string error 
•  Invalid syntax within serial sensor control string 
 
  E116 – Cannot log: detailed description 
•  The DT80 cannot log data for one or more schedules 
for the indicated reason 
•  If the problem was that an existing job of the same 
name had logged data/alarms then you need to give the 
new job a different name, or delete the old job’s data 
using DELDATA/DELALARMS 
   
 
  E117 – Incompatible schedule store units and 
  trigger 
•  You can only specify storefile size by time (e.g. 12 
hours data) if the schedule trigger is time based. 
 
  E118 – Error accessing drive 
x
: 
detailed 
  description 
•  The indicated drive (A: or B:) could not be accessed 
•  Media may be absent, not formatted or faulty. 
 
 
  E119 – No matching storefiles found 
•  There are no storefiles for the specified job/schedule 
 
  E122 – Command incompatible with configured 
  port function 
•  nSERIAL channel or trigger defined, or SSDIRECT 
command used, and specified serial port has not been 
configured as a serial channel in the profile 
 
  E123 – SSDIRECT mode already active 
•  SSDIRECT command was issued but SSDIRECT mode 
is already active on another comms port. Use 
ENDSSDIRECT to cancel SSDIRECT mode. 
 
  E124 – Modbus transaction failed 
•  could not establish connection to Modbus slave device, 
or no response to request 
 
  E125 - Modbus - write attempt to read-only 
  register 
•  Modbus discrete inputs and input registers (types 1 and 
3) cannot be written to using an expression 
 
  E126 - Modbus not supported on this channel 
•  Modbus channel should be 1,2,3 or 4 
 