RG 
Controls vs. Profiles 
The following table summarises the mapping between the controls described in this section and the DT80 profile 
settings, which are discussed in Profile Settings (P264) and throughout this manual. 
Category 
Control 
Default 
Equivalent command language setting and default 
Site 
information 
Name   
PROFILE USER SITE= 
Regional 
Mains frequency  50Hz 
PROFILE PARAMETERS P11=50 
Temperature units 
°C 
PROFILE PARAMETERS P36=0 
Decimal point char  Standard 
PROFILE PARAMETERS P38=46 
Time & date 
Time zone 
0 
PROFILE LOCALE TIME_ZONE=0S 
Use NTP 
no 
PROFILE NTP BACKGROUND_ENABLE=NO 
NTP server  0.datataker.pool.ntp.org 
PROFILE NTP SERVER=0.datataker.pool.ntp.org 
Update clock every 
3599 s 
PROFILE NTP BACKGROUND_PERIOD=3599S 
Statistics  Stat. schedule rate  1s 
RS1S 
CEM 
Number of CEMs 
0 
- 
Power 
Allow sleep 
yes 
PROFILE PARAMETERS P15=0 
Delay until sleep  30 s 
PROFILE PARAMETERS P17=30 
Disable sleep if ext power 
yes 
PROFILE PARAMETERS P15=0 
Disable sleep if Eth/USB  yes 
PROFILE PARAMETERS P15=0 
Power analog subsystem 
only when taking a reading 
PROFILE PARAMETERS P21=0 
Display backlight 
on when key pressed 
PROFILE PARAMETERS P20=2 
12V power output 
on when taking CEM 
reading 
PROFILE PARAMETERS P28=0 
Security 
Command server 
enabled 
PROFILE COMMAND_SERVER PORT=7700 
FTP server 
enabled 
PROFILE FTP_SERVER PORT=21 
HTTP server  enabled (fixed) 
PROFILE HTTP_SERVER PORT=80 
Modbus server 
enabled 
PROFILE MODBUS_SERVER TCPIP_PORT=502 
FTP username  DATATAKER 
PROFILE FTP_SERVER USER=DATATAKER 
FTP password 
DATATAKER 
PROFILE FTP_SERVER PASSWORD=DATATAKER 
Anonymous FTP 
enabled 
PROFILE FTP_SERVER ALLOW_ANONYMOUS=YES 
Command password   
PASSWORD= 
Command timeout 
600 s 
PROFILE PARAMETERS P14=600 
USB port  Function  command 
PROFILE USB_PORT FUNCTION=COMMAND 
Host port  
Function 
command 
PROFILE HOST_PORT FUNCTION=COMMAND 
Data rate 
57600 
PROFILE HOST_PORT BPS=57600 
Data bits  8 
PROFILE HOST_PORT DATA_BITS=8 
Stop bits 
1 
PROFILE HOST_PORT STOP_BITS=1 
Parity  none 
PROFILE HOST_PORT PARITY=NONE 
Flow control 
software 
PROFILE HOST_PORT FLOW=SOFTWARE 
Flow control timeout 
60 s 
PROFILE PARAMETERS P26=60 
Sensor port 
Function  serial sensor 
PROFILE SERSEN_PORT FUNCTION=SERIAL 
Data rate 
1200 
PROFILE SERSEN_PORT BPS=1200 
Data bits  8 
PROFILE SERSEN_PORT DATA_BITS=8 
Stop bits 
1 
PROFILE SERSEN_PORT STOP_BITS=1 
Parity 
none 
PROFILE SERSEN_PORT PARITY=NONE 
Mode  RS232 
PROFILE SERSEN_PORT MODE=RS232 
Flow control 
none 
PROFILE SERSEN_PORT FLOW=NONE 
Flow control timeout  60 s 
PROFILE PARAMETERS P26=60 
Ethernet 
Enable 
yes 
PROFILE ETHERNET ENABLE=YES 
Auto-config 
yes 
PROFILE ETHERNET IP_ADDRESS=AUTO 
Static IP address  0.0.0.0 
PROFILE ETHERNET IP_ADDRESS=AUTO 
Subnet mask 
255.255.255.0 
PROFILE ETHERNET SUBNET_MASK=255.255.255.0 
Gateway address  0.0.0.0 
PROFILE ETHERNET GATEWAY=0.0.0.0 
Primary DNS 
0.0.0.0 
PROFILE NETWORK DNS_SERVER_1=0.0.0.0 
Secondary DNS 
0.0.0.0 
PROFILE NETWORK DNS_SERVER_2=0.0.0.0 
Ethernet 
Email 
From name   