Specifications

Engineering Standard NSW
Signalling SMS 02
Cerberus Level Crossing Monitor Equipment
March 2005 Version 1.2 © Australian Rail Track Corporation Page 60 of 118
This document is uncontrolled when printed.
8. Use the menus to find and perform the required tasks.
Method 2
1. Power up the PC and plug the serial cable into serial port A or
COM1: on the PC and channel B on the Level Crossing Monitor.
2. Move to the desired directory and type LX_MAINT and press the
<enter> key.
3. Press <enter> to clear startup screen.
4. A menu will appear. Type 1 and press <enter> to select the
Connect menu.
5. Type 1 and press <enter> to Set Serial Port on the PC.
6. Type '1' to select serial port 1 (com1:) on the PC.
7. Type 9600 and press <enter> to change the bit rate.
8. Press <enter> 4 more times to accept the other default serial
port settings or type in the required values. You should not have
to change these settings.
9. Type 3 and press <enter> to Establish a connection with the
level crossing monitor.
10.A response will be displayed that shows details of the particular
Level Crossing Monitor with which you have established a
connection. If a error message occurs then try another method.
11.Type Q and press <enter> to return to the main
menu. 12.Use the menus to find and perform the
required tasks.