Specifications

Engineering Standard NSW
Signalling SMS 02
Cerberus Level Crossing Monitor Equipment
March 2005 Version 1.2 © Australian Rail Track Corporation Page 11 of 118
This document is uncontrolled when printed.
No remote or local test of the level crossing has occurred within the last
36 hours.
The local test was not valid as it was not conducted for the 2 minute
minimum period.
No train has traversed the level crossing within the last 72 hours.
The Emergency switches have been turned off for more than 10
minutes.
There has been a failure of some signalling equipment near the level
crossing which has caused a Interlocking failure. eg. points detection
failure, signal lamps out or track failure.
A status indication of WARNING & LAMP is indicated if:
One of the lamps is not working.
A status indication of WARNING & BATTERY is indicated if:
The AC Supply has been OFF for more than 6 hours 30 minutes.
A status indication of WARNING & SYS_FAULT is indicated if:
The Level Crossing Monitor itself has a internal fault. A possible
internal fault could be due to failure of the A/D card, real time clock,
CPU, memory, log data or EPROM.
A status indication of FAULT & LOGIC is indicated if the level crossing
has:
not started operating 6 seconds after the time that it should start
operating.
not stopped operating 6 seconds after it should have stopped
operating.
not had a change of state on the flasher inputs within the last 5
seconds when the level crossing should be operating.
operated continuously for more than 20 minutes.
remote battery testing output on without a test being requested or the
test runs for more than 5 minutes and 30 seconds.
the Boom normal when it should not be, or not normal when it should
be normal.
either direction stick is up and their is no train detected.
Battery Test relay is faulty
A status indication of FAULT & LAMP is indicated if:
Two or more of the lamps are not working.