Specifications
RailCorp Engineering Manual — Signals — Equipment Manual
Cerberus Level Crossing Monitor Field Equipment Manual TMG E1261
© RailCorp Page 58 of 89
Issued August 2012 UNCONTROLLED WHEN PRINTED Version 2.1
Additional buried cables to adjacent signalling locations are not normally cost justifiable to
provide the normal or additional inputs into the Level Crossing Monitor.
It is not desirable to use of the Level Crossing B12 or B15 supply for inputs outside the
Level Crossing Hut. This may however be accepted on a case by case basis.
Standard circuit sheet X015 details the types of inputs to be provided to the Level
Crossing Monitor and their preferred input numbers. It includes all the inputs for a double
line crossing with signals.
Inputs 1 to 8 should always be used for their nominated purpose and if the input is not
available then it should be left spare.
Inputs 9 to 12 should be used for any readily available Signals, Ground Frames, or Points
etc so that their operation may be logged.
Inputs 13 to 23 should always be used for their nominated purpose and if the input is not
available then it should be left spare.
Inputs 24 to 31 may be used for any purpose. The inputs detailed are a suggestion only.
It is normal for Country Level Crossings to have the DSPR on input 28, DSJR on input
29, DSJPR on input 30.
When applying Standard circuit sheet X15 to a particular Level Crossing the designer
must check:
When applying Standard circuit sheet X026 to a particular Level Crossing the designer
must check is their is a NO Charge relay provided with the Store 74. If there is not then
one needs to be provided.
5.1.2 Battery Test Outputs
Circuit sheet X14 shows the connections for the LX Monitor. The 8-way Output
Optoisolator terminals 1 & 8 are used to control the remote battery test. The outputs
switch to B12 to start a remote battery test. Both outputs are used instead of only one to
minimise the risk of a false remote battery test failing the battery.
5.1.3 Battery Test Relay
The Battery Test Relay is a Q type, 12 volt QBCA1. The heavy duty contacts of this relay
are designed to carry a DC current of at least 30A for a minimum of 10 seconds on a 50%
duty cycle. It is capable of breaking a current of 30A without damaging the relay. The
normal duty contacts of this relay are rated 18V- 250V Switching AC Inductive and 3
Amps continuous.
The heavy duty contacts place a load resistor across the level crossing battery, see sheet
X25. Two back contacts of this relay disconnect the STORE 74 Battery Charger for the
duration of the test. The Battery Charger will draw a maximum of 3 Amps which is well
below the current capacity of these two parallel back contacts. A front contact of this relay
is also fed into the LX monitor for detection purposes.
5.1.4 Non-Vital Timer
The Non-Vital timer circuit is shown on sheet X25 of the Standard Circuits. The CUT OFF
Timer is a delay ON timer set for 300 seconds. The unit is an industrial quality timer
designed for critical timing applications. It is used to stop the Battery test if the test
continues for significantly longer than the Battery test should last for. The CUT OFF
Timer de-energises the TEST CUT OFF Relay to stop the test.