Specifications
RailCorp Engineering Manual — Signals — Equipment Manual
Cerberus Level Crossing Monitor Field Equipment Manual TMG E1261
© RailCorp Page 51 of 89
Issued August 2012 UNCONTROLLED WHEN PRINTED Version 2.1
3.4 Incident Investigation
The following actions are to be taken in the event of an incident at a level crossing which
has an operational level crossing monitor:
a) Do not disturb the monitor. Note the state of all indicators on the front panel of
the monitor.
b) Make a physical inspection of the monitor and interface equipment.
c) If the monitor is physically damaged priority is to be given to recovery of the
large DALLAS IC's in positions U6 and U7 on the SCADA 2000 A I/O Board. If
these IC's are recovered intact then the log may be retrieved and analysed by
Signal Engineering. The EPROM in U5 should also be retrieved if possible.
d) If the monitor is undamaged and operating correctly than connect a portable PC
to the monitor and capture a full copy of the event log on the PC.
e) Note the accuracy of the monitors time and date.
f) Reset any alarms or warnings.
g) Examine the log for the time of the incident.
h) Perform any tests required to prove or disprove that the monitor is functioning
correctly. This may be best performed by repeating the commissioning tests.
i) Check that both used and unused inputs and outputs are shown by the monitor
to be in their actual state. Inputs are to be corresponded to the monitor. This is
best done by enabling reporting changes on the appropriate serial channel and
watching the changes occur on the PC screen when the inputs states are
changed. Cause each input to change to both possible states in turn. This must
be done by energising or de-energising the relays etc. For example pull the
negative pin for the XR. Then restore it. Note that additional changes will occur
and the tests need to be structured to correspond each event.
j) Confirm the battery voltage displayed by the monitor is correct within a
tolerance of +/- 0.30 volts. Measure the battery voltage at the battery terminals.
Then get the IO states from the monitor to find the monitors measured battery
voltage. Record these values and the battery offset.
k) Note down the lamp offset voltages currently in use.
l) Correspond the lamps This is best done by enabling reporting changes on the
appropriate serial channel and watching the changes occur on the PC screen
when the a lamp is removed or restored. Operate the crossing then correspond
one lamp from each lamp stand.
m) Select lamp diagnostics mode. While the crossing is not operating, check that
no lamp diagnostic information is displayed for any lamp channel. While the
crossing is operating check that the correct number of lamps is reported at least
95% of the time. If not examine lamp adjustment, lamp types.
n) Under no circumstances is the configuration of the monitor to be changed or
adjustments altered until the investigation is complete.
4 Fault Diagnosis
The following sections list fault conditions and the things to check for to identify their
cause.