Specifications

RailCorp Engineering Manual — Signals — Equipment Manual
Cerberus Level Crossing Monitor Field Equipment Manual TMG E1261
© RailCorp Page 39 of 89
Issued August 2012 UNCONTROLLED WHEN PRINTED Version 2.1
2.8.3 DPX-224 Modem
For the Dataplex DPX-224 the following commands the following modem initialisation
string is required.
AT &F &C1 &D0 S0=2 Q1 E0 B0 X0 &W
The DPX-224 modem requires the serial port A to be set at 1200bps or 2400bps.
2.8.4 Maestro Executive 144FM Modem
For the Maestro Executive 144FM the following commands the following modem
initialisation string is required.
AT &F &C1 &D2 S0=2 Q1 E0 &K0 %C0 \N0 T L1 &W0
Serial port A is set for 9600bps to provide consistency.
This modem should not be used with normal level crossing monitor installations as it
normally operates from 240V AC. This modem uses a 240V AC - 9 VDC plugpack to
power the modem. This modem may be able to be used with a level crossing monitor
installation by operating the modem off the sensor supply or off the level crossing battery
supply using a regulator unit.
2.8.5 Modem Replacement
If the modem answers and you are unable to communicate with the monitor then turn the
modem off, wait 5 seconds and then turn it back on. The modem is reconfigured by
ensuring the modem is plugged into serial port A and resetting the level crossing monitor
(resetting the monitor by turning it off and back on OR by pushing the reset pushbutton
on the I/O card).
If turning the modem off then on and re-configuring it does not correct the fault then
replace the modem.
Turn the power off to the modem via the switch on the back of the modem or by
disconnecting the connector. Disconnect the power leads, unplug the telephone line and
the serial cable. Re-connect the new modem taking special care with the polarity of the
power leads positive and negative. The positive lead has a red strip running down the
length of the wire.
Turn the new modem on via the switch on the back of it or by inserting the connector. Re-
configure the modem by resetting the Level Crossing monitor (red push button in the
middle of the I/O Board). Watch the modem. The TX data LED should flash when it is
reconfigured.
The Dataplex DPX-223 modems are no longer available new from Dataplex. The
DPX-213 (10-20V DC version) should be used as a replacement.
2.8.6 Other Brand Modems
Modem designs are changing at a rapid pace. Manufacturers are designing new features
into their modem products which may not be compatible with existing monitor/modem
installations. Not all modems are the same and their can be problems with connecting
different brand modems especially on the poor phone line encountered in country areas.
Please contact Signal Engineering for advice on different modems and possible
replacement modems.
Maestro Jetstream Series 3, Uses a Lcent Chip Set.