Specifications
RailCorp Engineering Manual — Signals — Equipment Manual
Cerberus Level Crossing Monitor Field Equipment Manual TMG E1261
© RailCorp Page 25 of 89
Issued August 2012 UNCONTROLLED WHEN PRINTED Version 2.1
inputs 2-8 is rare but each input can be checked by monitoring the analogue inputs (by
viewing I/O inputs) and connecting 5 volts to each input and confirming that the A/D
reading is close to 255.
The ADC board will also fail if the internal +12V rail fails or goes low voltage. The ADC
board uses this +12 VDC rail to generate a voltage reference. If the +12V rail fails than
the ADC will read zero on all of its inputs. (Note: it is possible for a failed current sensor
or faulty wiring to the sensor supply terminals 1-11 to fail the internal +12V rail and
therefore fail the ADC board.
2.2.4.5 Replacement Procedure
Open lid of the Level Crossing Monitor. Turn off the power. Unplug the cable. Remove
the screw and unplug the ADC module from the SCADA 2000 A I/O board.
Plug in the new module. Re-install the screw and plug in the cable ensuring that the cable
captive clips are engaged.
2.2.5 Backplane
2.2.5.1 Function
The backplane provides the interconnections for the power, digital, and other wiring.
2.2.5.2 Operation
The backplane is a passive device which provides various connectors and
interconnections between them via Printed Circuit Board (PCB) tracks. The backplane
does have a 5.1 VDC transzorb and a diode which is designed to suppress voltage
spikes from the +5 VDC supply and protect against reverse polarity.
2.2.5.3 Configuration and Set-up
The configuration links on the backplane are not used by the level crossing monitor. They
should however be set to the following:
• 375 kbps link set (link between the two bottom pins)
• The node address connections should be left as set by the factory.
2.2.5.4 Troubleshooting
If the backplane is suspected then it is best to test it by continuity testing the relevant
circuits on the backplane. If this is okay test for shorts to test circuits. Close inspection
can only be done by removing the backplane PCB as there are printed circuit board
tracks on both sides of the PCB.
It has been discovered that the 5.1V transzorb designed to protect the 5V supply is
susceptible to failing short circuit after a power surge or lightning strike hits the level
crossing location. If this transzorb has failed short circuit than the level crossing monitor
will draw excessive current blowing the 4A supply fuse. As a temporary measure you can
disconnect the failed transzorb with a pair of side cutters. The level crossing monitor may
then function correctly, although other components on the surge protection and power
supply board may have failed open circuit or PCB tracks may be damaged.