Instruction manual

6-1 Datalogic Automation, Inc.
CHAPTER 6
Appendix
Using Older Terminal Blocks
IMPORTANT: This section describes how to connect M-Series cameras using the older, discrete style of terminal block.
To use the newer, integrated style of terminal block, see “Connecting the Camera” on page 3-8.
WARNING: Never wire M1xx Camera Strobe Outputs in parallel with M1xx, M2xx, or M3xx Camera Strobe Outputs.
This will damage the cameras.
M1xx Camera Connection (Older Terminal Blocks)
Camera power, trigger signals, and strobe triggers can be connected to the camera using one of
two methods: a terminal block and cable or an unterminated cable only. To use a terminal block
(248-0140) you must also use the optional Hirose 6-pin to DB9 camera cable (606-0674-xx).
To connect the camera using an unterminated cable, use the optional Hirose 6-pin to unterminated
cable (part number 606-0672-xx).
Terminal Color Signal Name Notes
1 Blue Camera Power VCC Do NOT apply power to this terminal if using Power
Over Ethernet (PoE)
+12 VDC (+-10%) @ 250 mA Max
Maximum: +13.2 VDC
Minimum: +11.3 VDC
2 Orange Camera Trigger In 0 to +24 VDC recommended
Off: 0 to +1.4 VDC
On: +2.2 to +24 VDC; 5 to 15 ma
Maximum +30 VDC
3 Green No Connection
4* Wht/
Grn
Strobe Trigger Out DO NOT APPLY ANY VOLTAGE DIRECTLY TO THIS
OUTPUT. DO NOT WIRE OUTPUTS IN PARALLEL.
5 Wht/
Org
I/O Ground
6 Wht/
Blu
Camera Power Ground
7* None Strobe VCC Based on Strobe requirement
Max: +30 VDC; 50 ma
(*Block contains 1k Ohm 2W resistor between termi-
nals 4 and 7)