Specifications
GWY-01-DNT-01 MANUAL – REV. 02        CHAPTER 5: 
       DEVICENET INTERFACE 
       PAGE 55 OF 67   
3.  Following execution of the command, the Gateway writes its response to the 
Input Controller Tag, starting with the 2-byte Produce Data Size, at 
Local:2:I.Data [2] and the actual data beginning at Local:2:I.Data [3]. It then 
increments the counter value at Local:2:I.Data [1]. This alerts the PLC to the 
new data available (the Gateway generated response, in this case). 
4.  After processing the response information, the PLC copies the counter from 
Local:2:I.Data [1] to Local:2:O.Data [0], which signals to the Gateway that the 
PLC has retrieved the response data. 
OUTPUT CONTROLLER TAG 
CONTROLLER TAG 
LOCATION AND DATA 
DESCRIPTION 
Local:2:O.Data [0] 
(4) The PLC copies the value at 2:I:Data[1] here to 
acknowledge receipt of the response 
Local:2:O.Data [1]  (1) The PLC increments this counter value after copying 
a command in Consume Data 
Local:2:O.Data [2] 
Consume Data Size 
Local:2:O.Data [3] 
First WORD of Consume Data (Command from PLC) 
Local:2:O.Data [xxx] 
xxx WORD of Consume Data 
INPUT CONTROLLER TAG 
CONTROLLER TAG 
LOCATION AND DATA 
DESCRIPTION 
Local:2:I.Data [0]  (2) The value at 2:O:Data[1] is copied here by the 
Gateway to acknowledge receipt of a command 
Local:2:I.Data [1] 
(3) The Gateway increments this counter to signal that a 
response is available 
Local:2:I.Data [2] 
Produce Data Size 
Local:2:I.Data [3] 
First WORD of Produce Data (Response from Gateway) 
Local:2:I.Data [xxx] 
xxx WORD of Produce Data 
NOTE: A ladder logic example illustrating the implementation of this handshaking 
strategy can be downloaded from the technical support area of the EMS website.