Installation manual
25-PIN CABLE ELECTRICAL CONNECTIONS 
65
5
5.3 ID-NET™ INTERFACE 
25-pin Name  Function 
23  ID+  ID-NET™ network + 
24  ID-  ID-NET™ network - 
7 GND  Ground 
5.3.1 ID-NET™ Cables 
The following instructions are referred to Figure 57, Figure 58 and Figure 59. 
  The general cable type specifications are: CAT5 twisted pair + additional CAT5 twisted 
pair, shielded cable AWG 24 (or AWG 22) stranded flexible. 
We recommend using
 DeviceNet cables (drop or trunk type) to the following reference 
standards: 
AN50325 – IEC 62026 
UL STYLE 2502 80°C 30V 
  Cable Shield MUST be connected to earth ground ONLY at the Master. 
  NEVER use ID-NET™ cable shield as common reference. 
  The ID-NET™ max cable length depends on the baudrate used, (see the Baudrate Table 
below). 
  For Common Power Connections use only 2 wires (23 and 24). 
-  DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do not 
put it together with AC cable): 
-  Wire dimensioning must be checked in order to avoid voltage drops greater than 0.8 
Volts. 
-  Cable should lie down as near as possible to the ID-NET™ cable (avoiding wide loops 
between them). 
  Scanner's chassis may be connected to earth. 
  Network inside the same building. 
Baudrate Table 
Baud Rate  125 kbps  250 kbps 
500 kbps 
1Mbps 
Cable Length  1200 m  900 m 
700 m 
* 
* Application dependent, contact your Datalogic Automation representative for details. 
NOTE 
The default ID-NET™ baudrate is 500 kbps. Lower ID-NET™ baudrates 
allow longer cable lengths. The baudrate is software configurable by 
authorized Datalogic Automation personnel only. 