Installation manual
INSTALLATION
3
3.3.3 ID-NET™ Interface
C-BOX 100/150 Pin Name Function
38 ID-NET+ High speed internal network+
36 ID-NET- High speed internal network-
39 GND Ground
ID-NET™ Cables
The following instructions are referred to Figure 25, Figure 26 and Figure 27.
• The general cable type specifications are: CAT5 twisted pair + additional CAT5 twisted
pair, shielded cable AWG 24 (or AWG 22).
We recommend using DeviceNet cables (drop or trunk type) to the following reference
standards:
AN50325 – IEC 62026
UL STYLE 2502 80°C 30V
• Cable Shield MUST be connected to earth ground ONLY at the Master.
• NEVER use ID-NET™ cable shield as common reference.
• The ID-NET™ max cable length depends on the baudrate used, (see the Baudrate Table
below).
• For Common Power Connections use only 2 wires (36 and 38).
• DC Voltage Power cable (VS – GND) should be handled as a signal cable (i.e. do not put
it together with AC cable):
- Wire dimensioning must be checked in order to avoid voltage drops greater than 0.8
Volts.
- Cable should lie down as near as possible to the ID-NET™ cable (avoiding wide
loops between them).
• Scanner's chassis may be connected to earth.
• Network inside the same building.
Baudrate Table
Baud Rate 125 kbps 250 kbps
500 kbps
1Mbps
Cable Length 1200 m 900 m
700 m
*
* Application dependent, contact your Datalogic Automation representative for details.
NOTE
The default ID-NET™ baudrate is 500 kbps. Lower ID-NET™ baudrates
allow longer cable lengths. The baudrate is software configurable by
authorized Datalogic Automation personnel only.
33