To ensure that the C-BOX functions without errors, the shield of the PROFIBUS
cable must be grounded.
Ensure that the PROFIBUS connector uses the pin assignments shown in par
2.5.2
Attach the PROFIBUS connector to the PROFIBUS interface socket on the
C-BOX 3X0 and secure the connector with the retaining screws.
For C-Box 310 models, it is advised to use up to two ferrites (type Stewart
28A2029-0A0) on the Profibus cable to reduce electrical noise.
2.5.4 C-BOX 3X0 Configuration for Profibus DP Slave Node
In order to setup the C-BOX 3X0, you need to install the function blocks in your PLC
programming software and configure it.
The procedure below can be generally applied for this purpose:
1. Start the PROFIBUS configurator on the DP Master.
2. Insert the CD with the device database files (.GSD) into the drive of the
programming device (usually a PC).
3. Load the .GSD file HMS_1810.GSD in the configurator.
4. Configure the C-BOX 3X0 (through WinHost) setting the parameters according
to the PROFIBUS network application as described in the configurator's Help
On-Line or User's Manual.
NOTE
Further information on PROFIBUS protocol and Flow control is
provided in the C-BOX 300/310 PROFIBUS document and Help On-
Line installed from the configuration CD provided in the C-BOX
package.