Installation manual

INSTALLATION
11
2
2.4.4 Multidrop Address Selection
For RS485 half-duplex interface connections, the scanner multidrop address should
be set using the rotary switches placed inside the C-BOX 200.
The valid address range is from 00 to 31. This value is read only at power-on; any
change at run-time has no effect.
If an invalid value is detected (32-99) the C-BOX cannot communicate with the
Multiplexer and the green LED remains off. Furthermore, the SEND command
configures the scanner using the previously configured valid scanner address.
UNITS
TENS
Figure 10 - Rotary switches