Specifications

68 209351 REV B Operations Manual, Redundant System Controllers
6.3 Restoring Factory Pre-set Settings on RCP2/FPRC
The Teledyne Paradise Datacom Redundant System Controller comes with factory-
preset settings specific to the default system specifications. This factory setup can be
restored at any time either automatically or manually.
Important: Automatic restoration will restore complete factory setup
(including COM settings and miscellaneous fault handling). Manual resto-
ration has to be done one item at a time and only settings critical to sys-
tem operation will be restored.
6.3.1 Automatic restore
To restore settings automatically, follow these simple steps:
1. On the front panel keypad, press the Main Menu key;
2. Select menu item 5.Options and press the Enter key;
3. Select menu item 2.Restore and press the Enter key;
4. Select menu item 2.Restore Fctry and press the Enter key;
Default factory setup is now restored; sequentially press "Main Menu" and "Enter" to
return back to the informative menu sublevel.
6.3.2 Manual restore
Manual setup restoration is dependant on the makeup of your specific system. To
undertake a manual setup restoration, follow these directions:
1. On the front panel keypad, press the Main Menu key;
2. Select menu item 3.Operation and press the Enter key;
3. Select menu item 3.System and press the Enter key;
4. Select the System menu item relevant to your system (i.e. menu item 4 for
Dual 1:1) and press the Enter key;
5. Press the Main Menu key;
6. Select item 4.Flt.Setup and press the Enter key;
7. Select menu item 1.Mjr.Faults and press the Enter key;
8. Select menu item 2.External if the controller is not supplying power to the
LNBs; Select menu item 3.Both if the controller must be configured as the
primary power source for LNBs;
9. Press the Enter key;
10. Press the Main Menu key;
11. Select menu item 6.Calibr. and press the Enter
key;
12. Select menu item 2.Fault Logic and press the Enter key;
13. Select menu item 1.Fault High and press the Enter key.