34 209351 REV B Operations Manual, Redundant System Controllers
3.3.2.3 Sys. Address
Sets the network address of the controller if used in a RS485 network. Address is
selectable from 1 to 255
3.3.2.4 Interface
This menu choice provides the selection of the physical interface of the main serial
port. Choose between RS-232, RS-485, IPNet (Ethernet) and SNMP interfaces.
3.3.2.5 IP Setup
This menu allows the user to select between the following menu items: IP Info (to
review all IP Net Settings as described in Section 7.6); or any of the following to adjust
the existing settings: Local IP; Subnet Mask; Default Gateway; and Local Port.
Selecting the ‘More’ option allows the user to adjust the settings for the following
parameters: Community Get; Community Set; Lock IP and Web Password.
3.3.3 Operations Menu
This section describes the basic setup parameters of the redundant controller. The
operation parameters can be accessed from the main menu. Press the Main Menu
key; select 3.Operation and press the Enter key. See Figure 3-7. The following
parameters are selectable.
3.3.3.1 System
Selects the logical state machine used by the controller. Available choices are 1:1
Redundancy; 1:2 Redundancy or 1:2 Phase Combined; Dual 1:1; or Single Switch.
3.3.3.2 Buzzer
Allows the user to enable or disable the audible alarm buzzer. The factory default is to
have the buzzer enabled.
Figure 3-7: Operation Parameters Menu
2.Com Setup1.Sys Info
2.Buzzer
3.Operation 4.Flt. Setup 5.Options
1.System
Main Menu
6.Calibr
3.Control 4.Switching 5.Priority 6.Stby Select
1. 1:1 2. 1:2 3. 1:1 Ph. Comb 4. Dual 1:1 5.Sngl Sw
1. Buzzer On 2. Buzzer Off
1. Local 2. Remote
1. Auto 2. Manual
1. POL 1 2. POL 2
1. Unit 1 2. Unit 2 3. Unit 3