Specifications
Model No: PDUA-SH1623-0801: PDUA-SV1623-1601: PDUA-SV3223-2403:
Number of Ports 8 16 24
Input Voltage 230v 230v 230v
Capacity 16A 16A 32A
Breakers 1CB 1CB 3CB
Interface RJ45 for Ethernet
Frequency 50 ~ 60HZ full range
LED Indicator Yellow LED: SSL is enabled / Green LED: IP address
Audible Warning: 1 beep per second
Overload: 3 beeps per second
Circuit Breaker: triggered-continuous beeps
Meter 3 Digitals
Warning and overload - Meter will flash once per second
Range: 0A ~ 20A (true RMS)
Resolution: 0.A ~ 20A: 0.1A
Precision: 0.A ~ 20A: +/- 2% +/-0.1 Amp
Operating Temperature 0 ~ 40°C
Storage Temperature -25 ~ 65°C
Humidity 0 ~ 90%
Height 1U (44mm)
Power Distribution Units - PDU
30
PDUA-Sx1623-xxxx: SNMP Switched POM PDUs with Current Meter
The DataBay SNMP switched PDUs provide remote power mangement solutions which allow I.T. administrators to monitor servers
and network devices should any power consumption issues arise.
These units allow remote and on-site power monitoring through event alerts by email, ‘TRAP’ (network notifications) and audible
alarm. Each unit’s built-in digital current meter will indicate the total power consumption of each power strip. Using the software
supplied, these units also provide remote on/off switching functionality.
Specifications:
www.databay.uk.com
• Free utility software for managing multiple PDUs
• Circuit Breaker power protection
• Low profile, slim design makes it easy to mount in server cabinets
• Real time, remote on/off power control of each unit
• LED on each unit to indicate power status
• Power-on sequencing to avoid in-rush of power
Features:
• Integrated web server manages real time current
consumption of PDU
• Built-in true RMS current meter
• Easy set up, meter display IP address
• Audible Alarm - 2 separate warning audible signals for
threshold warning and overload
• Email and SNMP traps sent when power exceeds warning
threshold or overload threshold