2-4 Configuring Enhanced PLC-5 Processors
To configure the processor for a master station using standard
communication, place the processor into program mode and follow
the steps below using your RSLogix
5 software:
1. Double-click on the Channel
Configuration file to bring up
the Edit Channel Properties
interface.
2. On the Channel 0 tab, choose
System (Master) for your
Communication Mode.
3. Configure the Serial Port,
Options, and Polling
parameters according to
Table 2.1.
4.
C
onfigure
O
ptions parameters
according to Table 2.1.
5. Configure the Polling
parameters according to
Table 2.1.
6. When all parameters are set,
click OK.
7. Create station lists (page 2-8).