User manual
Publication AG-UM008C-EN-P - February 2005
D-6 Worksheets
Worksheet 2.2
Enhanced PLC-5 DF1
Half-Duplex Master Station
Configuration Using
Message-based
Communication
Use this worksheet to record your station’s configuration. For
descriptions of each line item, see page
2-11.
Page 1 of 1
Tab Parameter Example Your Configuration
Serial Port Remote Mode Change DISABLED
Diagnostic File N19
Baud Rate 9600
Bits Per Character 8
Stop Bits 1
Control Line HALF DUPLEX WITHOUT
CONTINUOUS CARRIER
Options Parity NONE
Error Detect CRC
Station Address 1
DF1 Retries 3
MSG Application Timeout
(x 20 ms)
1
RTS Send Delay (x 20 ms) 0
RTS Off Delay (x 20 ms) 0
ACK Timeout (x 20 ms) 15
Reply MSG Wait (x 20 ms) 5
Polling Polling Mode MESSAGE BASED (ALLOW SLAVES
TO INITIATE MESSAGES)