User guide

DATA-LINC GROUP
20
PN 161-09889-001B
rev 3/2005 ver 6.33c
PLR580D / DA User Guide
6. The unit will now ask for the number of ADs (analog inputs) on each Remote. ‘#ADsSlv0’. The question is repeated
for each Remote unit. ‘#ADsSlv1’.etc. Any units that have no (zero) active analog channels must be put after any
remotes that do have analog channels. Enter the number of analogs channels for each Remote.
7. The display now asks for the number of analog inputs at the Master unit. ‘0-8 MstrAD’ The number of master analog
inputs must equal the total number of analog inputs entered for each remote in step 6 above.
8. The display now asks for the number of analog outputs on each Remote ‘#DAsSlv0’. The question is repeated for
each Remote unit. ‘#DAsSlv1’ etc. These values must be the same as the numbers entered in step 6 above.
9. The display now asks for number of analog outputs at the Master unit. ‘0-8 MstrDA This number is the same as
entered in step 7 above.
10. The display now prints out a status of your entries. Write these down and keep for use when you call Data-Linc
Group technical support. Note the first line may say Master or Slave/Remote. Review the settings. The EEprom
has been changed. The print out has been read from the changed EEprom. The data shown is from a master unit.
The Remote display is similar.
Mstr EEP:
B# AD DA Slvs
5 3 3 3
ADs/Slave 1 2 0 0 0 0 0 0
DAs/Slave 1 2 0 0 0 0 0 0
Check
11. Remove DC power, remove the serial cable, replace the jumpers on P1 and P2 back to the RUN/NORMAL position.
Repeat the procedure for all of the units that you are reconfiguring.
12. After all units are changed, bench test the system. The most likely problem is the baud rate setting does not match
the setting in the radio modules.