Unit installation
Controls
SCXF-SVX01K-EN 63
• Occupancy bypass time
• Outdoor air damper minimum position setpoint
• Outdoor air relative humidity
• Outdoor air temperature
• Unit start delay time setpoint
• Zone temperature
• Zone temperature setpoint
• Zone temperature setpoint (default)
• Zone temperature setpoint limits
• Zone temperature setpoint offsets
• Zone temperature setpoint shift
Analog outputs
• Alarm message
• Building static pressure status
• Condenser saturated refrigerant temperature
• Condenser water temperature
• Cooling output status
• Effective occupancy
• Exhaust fan status
• Heating output status
• Heating/cooling mode
• Morning warm up sensor temperature
• Outdoor air damper position
• Outdoor air enthalpy
• Outdoor air relative humidity
• Return air temperature
• Supply air temperature
• Supply fan status
• Unit status mode
• Zone CO2
• Zone relative humidity
Variable Air Volume (VAV)
Binary Input
• Airside economizer enable/disable
• Condenser water flow input
• Emergency override
• Local fan switch enable/disable
• Mechanical cooling lockout
• Mechanical heating lockout
• Occupancy
Binary Outputs
• Airside economizer status
• Alarm status
• Compressor on/off status
• Condenser circuit information
• Condenser type (water or air cooled)
• Condenser waterflow status
• Condenser waterflow status
• Condenser water pump status
Analog Inputs
• Airside economizer dry bulb setpoint
• Airside economizer minimum position
• Building static pressure input
• Building static pressure setpoint
• Daytime warm up setpoint
• Daytime warm up terminate setpoint
• Maintenance required time
• Occupancy bypass time
• Outdoor air damper minimum position setpoint
• Outdoor airflow minimum setpoint
• Outdoor air relative humidity
• Outdoor air temperature
• Supply air cooling setpoint
• Supply air cooling setpoint (default)
Analog Outputs
• o Building static pressure status
• o Alarm message
• o Condenser saturated refrigerant temp.
• o Condenser water temperature
• o Condenser water temp (local)
• o Cooling output status
• o Exhaust fan status
• o Heating output status
• o Heating/cooling mode
• o Mixed air temperature
• Morning warm up sensor temperature
• Outdoor air damper position
• Outdoor air enthalpy
• Outdoor air flow
• Outdoor air relative humidity status
• Outdoor air temperature status
• Return air temperature
BCI-I option
For BACnet® Points List refer to ACC-SVP01*-EN