Unit installation

62 SCXF-SVX01K-EN
Controls
Points List
RTM Module
Binary Inputs
Emergency stop
External auto/stop
Unoccupied/occupied
Dirty filter
VAV changeover with hydronic heat
Binary outputs
VAV box drive max (VAV units only)
CV unoccupied mode indicator (CV units only)
Alarm
Fan run request
Water pump request (water-cooled only)
Analog input
Airside economizer damper minimum position
Analog output
Outside air damper actuator
Heat Module:
Analog output
GBAS Module
Binary inputs
Demand limit contacts
Binary outputs
Dirty filter relay
Refrigeration fail relay
Heat fail relay
Supply fan fail relay
Active diagnostics
Analog inputs
Occupied zone cooling setpoint
Occupied zone heating setpoint
Unoccupied zone cooling setpoint
Unoccupied zone heating setpoint or minimum
outside
air flow setpoint
Supply air cooling setpoint
Supply air heating setpoint
Supply air static pressure setpoint
ECEM Module
Analog inputs
Return air temperature
Return air humidity
In addition, units with a VOM have:
Binary inputs
VOM mode A, unit off
VOM mode B, pressurize
VOM mode C, exhaust
VOM mode D, purge
VOM mode E, purge w/duct pressure control
Binary output
V.O. relay
Tracer /LCI-I option
Constant Volume (CV)
Binary inputs
Airside economizer enable/disable
Condenser type (air or water cooled)
Condenser water flow status
Emergency shutdown
Local fan switch enable/disable
Mechanical cooling lockout
Mechanical heating lockout
Mixed air temperature
Occupancy
Occupancy override
Occupancy sensor
Binary outputs
Airside economizer status
Alarm status
Compressor on/off status
Condenser circuit information
Condenser water pump status
Waterside economizer status
Analog inputs
Airside economizer dry bulb setpoint
Airside economizer minimum setpoint
Building static pressure input
Maintenance required time