Unit installation
General Data
SCXF-SVX01K-EN 13
Table 3. SCRF/SIRF Air-cooled self-contained
Unit Size 20 25 29 30 35 40 50 60
Compressor Data
Quantity 2 1/1 1/1 3 3 2/1 3 4
Nominal Ton/Comp 10 15/10 15/10 10 10 10/15 15 15
Circuits 2 2 2 22222
Evaporator Coil Data
Rows 32434446
Sq. Ft. 21.81 29.98 29.98 31.35 31.35 38.57 49.09 49.09
FPF 144 144 144 120 144 144 144 144
Evaporator Fan Data
Quantity 1 1 1 11111
Diameter (in.) 18 18 18.25 20 20 25 25 27.5
Minimum hp 5 5 5 5 5 7.5 10 10
Minimum kW (3.73) (3.73) (3.73) (3.73) (3.73) (5.59) (7.46) (7.46)
Maximum hp 20 20 20 25 25 30 40 50
Maximum kW (14.91) (18.64) (18.64) (18.64) (18.64) (22.37) (37.29) (37.29)
Minimum Design cfm 6500 8700 8700 9100 9880 11960 15080 20800
Maximum Design cfm 10625 12325 13600 14875 16150 19550 24650 29800
General Data
EER 10.0 10.0 10.5 10.4 10.6 10.7 10.5 10.3
IEER (CV) 10.8 11.6 12.2 12.5 12.0 12.7 12.1 11.2
IEER (VAV) 11.9 12.8 13.7 13.5 13.9 14.4 13.7 14.1
Refrigerant Charge See Note 6
Capacity Steps - % 100/53/0 100/62/39/0 100/59/39/0 100/65/31/0 100/65/30/0
100/70/41/
30/0
100/65/30/0
100/73/46/
20/0
CCRC/CIRC Unit Match 20 29 29 35 35 40 50 60
Notes:
1. Compressors are Trane 3-D™ scroll.
2. EER and IEER are rated in accordance to ARI Standard 340/360-2007. Based on 80/67° F (26.7/19.4 °C) to evaporator coil, nominal airflow and 85-
95 °F (29.4/35 °C) condenser water.
3. All units operate with R-410A.
4. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
5. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
6. Units ship with Dry Nitrogen Charge. Field refrigerant system charge required. Refer to Table 5, p. 14 for amounts required.