Unit installation
General Data
12 SCXF-SVX01K-EN
Table 2. SCWF/SIWF Water-cooled self-contained, 46-110 tons
Unit Size 46 52 58 65 72 80 90 100 110
Compressor Data
Quantity 2/1 3 3 3/1 3/1 4 5 2/4 6
Nominal Ton/Comp 10/15 15 15 15/10 15/10 15 15 10/15 15
Circuits 3 3 3 4 4 4 5 6 6
Evaporator Coil Data
Rows 4 or 6 2 4 or 6 3 4 or 6 6 6 6 6
Sq. Ft. 38.57 49.09 49.09 49.09 49.09 49.09 56.81 56.81 56.81
FPF 144 144 144 144 144 144 144 144 144
Condenser Data
Min gpm w/o Econ 64 84 84 102 102 112 140 168 168
Min gpm w/ Econ 64 84 84 102 102 112
Maximum gpm 142 186 186 226 226 248 300 350 350
Evaporator Fan Data
Quantity 1 1 1 1 1 1 1 1 1
Diameter (in.) 25 25 25 27.5 27.5 27.5 27.5 27.5 27.5
Minimum hp 7.5 7.5 7.5 10 10 10 15 15 15
Minimum kW (5.59) (7.46) (7.46) (7.46) (7.46) (7.46) (11.19) (11.19) (11.19)
Maximum hp 30 40 40 50 50 50 60 60 60
Maximum kW (22.37) (37.29) (37.29) (37.29) (37.29) (37.29) (44.74) (44.74) (44.74)
Min Design cfm 11960 14250 15080 16900 18700 20800 17500 17500 17500
Max Design cfm 19550 22100 24650 27625 29800 29800 35000 35000 35000
High Capacity Option
Rows 6 — 6 — 6 — 8 8 8
Optional Low Flow Fan*
Diameter (in.) 18 — 18 — 20 — — — —
Min./Max Design cfm 7700/13600 —
8900/
13600
—
10700/
16150
—— — —
General Data R-410A
EER 14.3 14.0 14.3 14.0 14.0 14.0 14.1 14.1 14.0
IEER (CV) 15.2 15.7 15.3 15.4 14.9 14.6 16.3 16.3 16.3
IEER (VFD) 18.8 17.9 18.9 18.2 18.5 19.3 18.6 18.5 18.1
Refrigerant Charge — lbs. R-410A
Circuit A 24.5 21.0 26.5 22.0 24.5 28.0 24.5 24.5 24.5
Circuit B 24.5 21.0 26.5 22.0 24.5 28.0 24.5 24.5 24.5
Circuit C 24.5 21.0 26.5 22.0 24.5 28.0 24.5 24.5 24.5
Circuit D – – – 21.0 22.0 28.0 24.5 24.5 24.5
Circuit E – – – – – – 24.5 24.5 24.5
Circuit F – – – – – – – 24.5 24.5
Capacity Steps - % 100/70/41/30/0
100/65/
32/0
100/65/
30/0
100/71/
44/24/0
100/71/43/
23/0
100/73/46/
20/0
100/80/40/
20/0
100/75/38/
19/0
100/66/33/
17/0
Notes:
1. Compressors are Trane 3-D™ scroll.
2. EER and IEER are rated in accordance to ARI Standard 340/360-2007. Based on 80/67° F (26.7/19.4 °C) to evaporator coil, nominal airflow and 85-
95 °F (29.4/35 °C) condenser water.
3. All units operate with R-410A. Units ships with full operating charge.
4. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
5. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
*Optional low flow fan (unit model number digit 23 = 1) is available ONLY when High Capacity option is selected (unit model number digit 5 = V).