Unit installation
General Data
SCXF-SVX01K-EN 11
General Data
Table 1. SCWF/SIWF Water-cooled self-contained, 20 to 42 tons
Unit Size 20 22 25 29 32 35 38 42
Compressor Data
Quantity 2 2 2 1/1 1/1 3 3 2/1
Nominal Ton/comp 10 10 10 15/10 15/10 10 10 10/15
Circuits 2 2 2 2 2 3 3 3
Evaporator Coil Data
Rows 2 2 3 or 6 2 4 or 6 3 4 or 6 3
Sq. Ft. 21.81 21.81 21.81 29.98 29.98 31.35 31.35 38.57
FPF 144 144 144 144 144 144 144 144
Condenser Data
Minimum gpm w/o Econ 36 36 36 46 46 54 54 64
Minimum gpm w/ Econ 41 41 41 60 60 65 65 64
Maximum gpm 80 80 80 102 102 119 119 142
Evaporator Fan Data
Quantity 1 1 1 1 1 1 1 1
Diameter (in.) 18 18 18 18 18 20 20 25
Minimum hp 5 5 5 5 5 5 5 7. 5
Minimum kW (3.73) (3.73) (3.73) (3.73) (3.73) (3.73) (3.73) (5.39)
Maximum hp 20 20 20 20 20 25 25 30
Maximum kW (14.91) (14.91) (14.91) (18.64) (18.64) (18.64) (18.64) (22.37)
Minimum Design cfm 6325 6325 6500 8700 8700 9100 9880 11200
Maximum Design cfm 8500 9350 10625 12325 13600 14875 16150 17850
High Capacity Option
Rows ——6—6—6—
Optional Low Flow Fan*
Diameter (in.) — — — — — — 18 —
Min/max Design cfm — — — — — — 6000/13600 —
General Data R-410A
EER 14.0 14.0 14.0 14.0 14.3 14.0 14.2 14.2
IEER (CV) 15.3 15.3 15.0 15.6 15.2 15.2 14.9 15.6
IEER (VAV) 17.4 17.4 17.5 18.1 18.8 18.0 18.5 18.3
Refrigerant Charge, lbs. R-410A
Circuit A 19.5 19.5 21.5 22.0 28.5 21.5 23.5 22.0
Circuit B 19.5 19.5 21.5 19.5 23.5 21.5 23.5 22.0
Circuit C – – – – – 21.5 23.5 22.0
Capacity Steps - % 100/53/0 100/53/0 100/53/0 100/62/39/0 100/59/39/0 100/65/31/0 100/65/30/0
100/71/
43/26/0
Notes:
1. Compressors are Trane 3-D™ scroll.
2. EER and IEER are rated in accordance to AHRI Standard 340/360-2010. Based on 80/67° F (26.7/19.4 °C) to evaporator coil, nominal airflow and
85-95 °F (29.4/35 °C) condenser water.
3. All units operate with R-410A. Units ship with full operating charge.
4. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.
5. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.
*Optional low flow fan (unit model number digit 23 = 1) is available ONLY when High Capacity option is selected (unit model number digit 5 = V).