Unit installation

Diagnostics
SCXF-SVX01K-EN 101
UCM Reaction:The minimum airflow control function is
disabled.The outside air damper minimum position
function reverts to using the O/A flow compensation
function if O/A flow compensation is enabled or to the
default minimum position function if O/A flow
compensation is disabled or not available.
Reset Required: (PAR) An automatic reset occurs after the
designated space pressure transducer sends a signal
within range for 10 continuous seconds.
VOM Communications Failure
Problem:The RTM has lost communication with the VCM.
Check: Field/unit wiring between RTM and VCM.
Reason for Diagnostic:The RTM has lost communications
with the VOM.
UCM Reaction: Ventilation override actions will not be
allowed, and the VO Output relay will be deenergized.
Reset Required: (PAR) An automatic reset occurs after
communication has been restored.
W
WSM Communications Fail
Problem:The RTM has lost communication with theWSM.
Check: Field/unit wiring between RTM and WSM.
Reason for Diagnostic: RTM has lost communication with
WSM.
UCM Reaction: UCM will react as if a freezestat has
occurred by issuing:
“all heat on or “mod output full open” request to “heat
control”
A “fan off” request to “supply fan control”
“close damper” request to “economizer actuator
control”
Water pump to turn on and position all water valves to
provide maximum flow through all water source heat
exchangers
Disables preheat function if WSM mixed air temp sensor
is selected as preheat sensor
Reset Required: An automatic reset occurs after one
complete set of IPC packets is received.
WSM Mixed Air Temp Sensor Fail
b. Activation Conditions: temperature <-50°F or
temperature >209°F, and sensor is selected for use by
“waterside economizer temperature enable function” or
“preheat function”
c.Time to React: 10 sec < T < 20 sec
e. Actions to be Initiated: “waterside economizer
temperature enable function” uses supply air cooling
setpoint instead of mixed air temperature. If mixed air
temperature is used for “preheat function”, issue a
“disable” request to “preheat function”.
f. Reset: An automatic reset occurs after mixed air temp.
input returns to within range continuously for 10 seconds.
Water Flow Fail
a. Data used (module,packet,byte,bit): WSM, 01,19, 05
b. Activation Conditions:Water flow input is detected open
1. at the end of precool water flow initiation state, or
2. continuously for five minutes while:
·water side economizer is open 100%,
· presetting of a head pressure valve, or
· demand for mechanical cooling.
Unit must be: a. configured with water cooled condenser
and/or water economizer and b. have water flow switch
installed.
c.Time to React: immediate
e. Actions to be Initiated: A “lockout all ckts” request is
issued to the “compressor staging function”
f. Reset: Automatic reset occurs after water flow input
returns to within range continuously for 3 seconds, water
pump is requested OFF, or water flow switch becomes not
installed.
Z
Zone Cool Setpoint Failure
Problem: Occupied zone cooling setpoint is out of range.
Reason for Diagnostic: Input designated as occupied zone
cooling setpoint source is out of range (temp. < 45°F or >
94°F).
UCM Reaction:The active occupied zone cooling setpoint
reverts to the default occupied zone cooling setpoint.
Reset Required: (PAR) an automatic reset occurs after
designated occupied zone CSP input returns to its
allowable range for 10 continuous seconds, or after a
different valid occupied zone CSP selection source is user-
defined.