Specifications
37
MODULAR DATA TEMP SERIES
8, 10, 13 ton DX Units
Guide Specifi cations
GENERAL
The environmental control units shall be provided with a high sensible cooling system, factory assembled, piped, wired, and run
tested prior to shipment and designed for the following air pattern:
___ Down Discharge
___ Top Discharge for Duct Connection
___ Top Discharge with Plenum
The system shall be designed for draw through air arrangement to insure even air distribution to the entire face of the coil.
Units shall be ETL or UL listed.
CABINET and FRAME
The frame shall be constructed of 14 gauge welded tubular steel and coated with a heavy corrosion inhibiting fi nish for long life.
All internal fans shall be of high grade steel and shall be coated and sealed for utmost protection against corrosion. The unit shall
have complete front and side access by means of high quality furniture grade steel doors with heavy duty hinges. The door shall
be lined with one inch (1”), 1-1/2 pound density fi berglass insulation. Each door shall be provided with sure close latches which
shall be quickly removable for easy access and a polyurethane gasket to prevent air leakage. The doors shall be painted to match
or contrast with other equipment in the space. Bypass air shall be provided around the cooling coil to prevent saturated air from
being distributed to equipment in the controlled space. The cooling coil shall sit in a stainless steel drain pan.
The unit shall be painted ______________________.
( color )
REFRIGERATION CIRCUIT
Air Cooled with Remote Outdoor Condenser - The refrigeration system shall be split type with an indoor evaporator section and
remote outdoor condenser. The indoor evaporator section shall include the cooling coil, compressor, humidifi er, reheat, fi lters and
controls. The cooling coil shall be in an “A” frame arrangement to allow maximum coil surface in a small cabinet. The large faced
area coil shall be constructed with
1
/2” O.D. copper tube with 12 fi ns per inch of corrugated aluminum for maximum heat transfer.
Maximum face velocity shall be less than 500 feet per minute. The expansion valve shall be of the adjustable thermostatic type
with external equalization. The compressor shall be hermetic scroll type, with complete overload protection on all three power
lines, internal thermostat for winding protection, crankcase heater, sight-glass and low pressure override timer for positive starting
at low temperatures. The fi lter drier shall be of the fl are fi tting type for non-torch servicing. The circuit shall contain high and
low pressure safety switches. The high and low pressure safety switches shall be installed with shraeder type fi ttings with valve
core.
Each system shall include a low profi le, slow speed, direct drive propeller fan type air cooled condenser. The air discharge shall be
vertical to minimize the effects of wind blowing through the coil at low ambient temperatures. The condenser shall be constructed
of aluminum and contain a
1
/2” O.D. copper tube coil with corrugated aluminum fi ns for maximum heat transfer. The condenser
shall have fan speed control with transducers to modulate the speed of the fi rst condenser fan motor and provide positive start-up
and operation at ambient temperatures to -20° F. Additional condenser fan motors are to be controlled by ambient thermostats.
All controls including the fan speed control shall be factory mounted in the air cooled condenser in an integral factory wired and
tested control panel. The air cooled condenser shall be manufactured by the manufacturer of the indoor unit.
GUIDE SPECIFICATIONS