Specifications

24
R-407C
WATER/GLYCOL COOLED: Performance data at OPTIONAL air ow
MODEL NUMBER DT*D/U-08 DT*D/U-10 DT*D/U-13
ELECTRICAL SECTION Standard Motor
Electrical data based on: electric reheat-YES, steam generator humidi er-YES, and STANDARD MOTOR.
208-230/3/60 FLA/MCA/MOP 80/97/110 94/113/125 106/129/150
460/3/60 FLA/MCA/MOP 38/46/50 43/52/60 48/58/70
575/3/60 FLA/MCA/MOP 29/36/40 33/40/45 40/48/60
Electrical data based on: electric reheat-NO, steam generator humidi er-YES, and STANDARD MOTOR.
208-230/3/60 FLA/MCA/MOP 54/65/90 68/82/110 80/97/125
460/3/60 FLA/MCA/MOP 27/32/45 31/37/50 36/44/60
575/3/60 FLA/MCA/MOP 20/24/30 24/28/35 30/37/50
Electrical data based on: electric reheat-YES, steam generator humidi er-NO, and STANDARD MOTOR.
208-230/3/60 FLA/MCA/MOP 80/97/110 94/113/125 106/129/150
460/3/60 FLA/MCA/MOP 38/46/50 43/52/60 48/58/70
575/3/60 FLA/MCA/MOP 29/36/40 33/40/45 40/48/60
Electrical data based on: electric reheat-NO, steam generator humidi er - NO, and STANDARD MOTOR.
208-230/3/60 FLA/MCA/MOP 38/45/70 52/61/90 64/76/125
460/3/60 FLA/MCA/MOP 19/23/35 24/28/45 29/35/50
575/3/60 FLA/MCA/MOP 14/17/25 18/21/30 25/29/45
 STANDARD MOTOR
Motor horsepower 3 5 5
208-230/3/60 FLA 9.0 14.6 14.6
460/3/60 FLA 4.4 6.6 6.6
575/3/60 FLA 3.3 5.3 5.3
COMPRESSOR
230/3/60 FLA 28.8 37.2 49.4
460/3/60 FLA 14.7 17.2 22.4
575/3/60 FLA 10.8 12.4 19.2
* - W for water or G for glycol
FLA - Full load amps
MCA - Minimum circuit amps (wire sizing amps)
MOP - Maximum overcurrent protection device amps