Specifications

24
Adjust the refrigerant charge until the sight glass clears or has only sparse bubbles. The unit
should be allowed to stabilize for several minutes before meaningful measurements can be taken
and the conditioned room should be at or near the temperature setpoint.
All water/glycol cooled units have a water regulating valve. A head pressure transducer is
connected to a shraeder tting on the discharge line and water is regulated into the condenser coil.
Plate n condensers are standard.
Before starting a compressor, the crankcase heaters should be energized for a minimum of 12
hours to reduce the possibility of liquid slugging on start-up. Failure to energize crankcase heaters
could result in compressor damage.
Note: Charging to a full liquid line sight glass should never be the sole means of determining the
correct refrigerant charge. Other parameters such as superheat, suction pressure, head pressure,
sub-cooling and ambient temperature are also important. A system charged to a clear sight glass
is often overcharged.
5.5 Refrigerant Handling
The use of recovery/recycling units is required by U.S. Environmental Protection Agency (EPA)
regulations. Technicians who service and dispose of air conditioning and refrigeration equipment
must recover the refrigerant instead of venting it to the atmosphere.
Except for extremely small releases of refrigerant such as what occurs when disconnecting
service hoses (diminimous release), a technician who knowingly releases or vents refrigerant to the
atmosphere is in violation of this regulation. Freon purchasers must be certi ed technicians and
have a valid EPA certi cation card.
6.0 GLYCOL SYSTEMS
6.1 Glycol Concentration
The system must be lled with water and the appropriate amount of ethylene or propylene glycol
to protect against winter freeze-up. To achieve the approximate glycol concentration, it is necessary
to know the total system volume. This consists of the sum of the uid cooler volume, the evaporator
unit volume, and the volume of the interconnecting piping.
The following tables can be used for arriving at an approximate system volume. After installation,
the glycol percentage should be checked. The glycol percentage should also be checked at regular
intervals to ensure freeze protection.