Specifications

23
Open the high side valve on the manifold only and allow the refrigerant to ow until the system
pressure equalizes. At this point the system will have 78-85% of the total refrigerant charge.
Start the (evaporator) motor(s). Start the compressor(s) and check the operating pressures and
temperatures.
A quick and easy way to run the blower and compressor is using the manual switches on the
unit’s microprocessor. Switch the blower and compressor manual switches to the ON position. All
automatic control is disabled but safety switches will remain functional.
Before starting a compressor, the crankcase heaters should be energized for a minimum of 12
hours to reduce the possibility of liquid slugging on start-up. Failure to energize crankcase heaters
could result in compressor damage.
Start the evaporator fan and verify the fan rotation. From a vacuum, add liquid refrigerant to the
high side of the system until the pressures equalize. Start the compressor. Check the liquid line
sight glass to get a feel for the approximate charge. Bubbles in the sight glass are not unusual at
this point and be caused by ashing from liquid pressure drop, low sub-cooling or low charge. It is
likely that more refrigerant will be required to complete the charging procedure.
If the receiver (head) pressure is below 350 PSIG for R-410A, block part of the condenser coil
surface until the pressure rises to 350 PSIG or higher. If the receiver (head) pressure is below 230
PSIG with R-407C, block part of the condenser coil surface until the pressure rises to 230 PSIG or
higher. During extremely cold weather all the condenser fans have to be de-energized to maintain
head pressure. Add refrigerant to the system until the ball in the sight-glass is at the 1/3 level.
After the system is allowed to stabilize, the superheat at the compressor suction line (reading from
at least 6 inches from the sight glass) should be 8 – 15°F. Remove any blocks that may have been
used on the condenser coil. If the ambient temperature is below 60°F, some of the refrigerant will
be backed up in the condenser coil causing the liquid level in the receiver to drop (this is normal).
Note: Charging to a full liquid line sight glass should never be the sole means of determining the
correct refrigerant charge. Other parameters such as superheat, suction pressure, head pressure,
sub-cooling and ambient temperature are also important. A system charged to a clear sight glass
is often overcharged.
5.4 Water/Glycol Cooled Systems
5.4.1 Water/Glycol Cooled Systems Charging
All water/glycol cooled units are factory charged with refrigerant. The water regulating valve
should be adjusted to maintain a discharge pressure between 340–390 PSIG for R-410A and 230-
260 for R-410A. Saturated suction pressure should be 100 PSIG or higher with R-410A and 58 PSIG
or greater with R-407C. The superheat at the compressor suction line at least 6 inches away from
compressor should be between 8-15°F.
Field charging water/glycol system should be done by referring to the unit electrical nameplate
for factory charge. Although this gure represents the original factory charge, it is still necessary
to measure and note proper unit operation including superheat, head and suction pressure. Some
adjustment to charge may be required.