Specifications

22
5.3 Air Cooled Systems
5.3.1 Fan Speed Control System Charging
The standard air cooled condenser provided with Data Aire equipment has fan speed control on
the lead motor (nearest the header). After the eld refrigerant piping is properly completed connect
the refrigerant drum to the low side and charge with vapor. (Refer to Section 2.6 LEAK TESTING
and Section 2.7 EVACUATION prior to charging the system.)
It is likely that more refrigerant will be required to complete the charging procedure (line runs
need to be taken into account). Make sure all hoses are properly purged. From a vacuum feed liquid
refrigerant into the high side of the system until the pressure equalizes. At this point there will be
about 70-80% of the total charge in the system.
Before starting a compressor, the crankcase heater should be energized for a minimum of 12
hours to reduce the possibility of liquid slugging on start-up. Failure to energize the crankcase heater
could result in compressor damage.
If the system is charged from a vacuum, the preheating of the compressor is not necessary. Start
the system and allow the system to stabilize to room temperature. Bubbles in the sight glass are not
unusual at this point and can be caused by ashing from liquid line pressure drop, low sub-cooling
or low charge. It is likely that more refrigerant will be required to complete the charging procedure.
Adjust the refrigerant charge until the sub-cooling is between 8 and 10°F. There may be ashing
and/or bubbles in the sight glass when the system is properly charged.
The system should be allowed to stabilize for 15 to 20 minutes before meaningful measurements
can be taken. After the system is allowed to stabilize, veri cation of a few key measurements should
be noted. The discharge pressure with R-410A should be between 340-415 PSIG and the sub-cooling
should be between 8-10°F depending on ambient conditions. Units with R-407C the discharge
pressure should be between 240-295 PSIG. Suction temperature should be 100 PSIG or greater
with R-410A and 58 PSIG or greater with R-407C. Measure the superheat at the compressor suction
line at least 6 inches away from the compressor. The superheat should be between 8-15°F.
Note: Charging to a full liquid line sight glass should never be the sole means of determining the
correct refrigerant charge. Other parameters such as superheat, suction pressure, head pressure,
sub-cooling and ambient temperature are also important. A system charged to a clear sight glass
is often overcharged.
5.3.2 Flooded System Charging
Flooded type systems are units having refrigerant circuits with an optional liquid receiver and head
pressure control valve. When the ambient temperature falls during cold weather, the head pressure
control valve will regulate the ow of refrigerant to ensure nearly constant receiver pressure. The
condenser is partially ooded with liquid in cold weather. In warm weather the extra refrigerant is
stored in the receiver.
Flooded systems require more refrigerant than fan speed control systems. Connect the pressure
gauge manifold set to the high and low ports near the compressor. Connect the charging line to
the refrigerant tank and set it for liquid feed. Open the refrigerant tank valve and purge the line.