Specifications
17
3.10 Condensate Probe
A condensate probe for sensing under fl oor water is included with this unit. This comes in a plastic
bag, with about 15 feet of coiled-up wire. The probe is a fl at plate that is typically placed below the
unit in a location where water is likely to accumulate.
Place the probe fl at on the fl oor on top of a thin layer of non conductive silicone. Secure the
attached wires where necessary. A longer length of wire may be used if required.
Note: Failure to uncoil the length of wire attached to the condensate probe can result
in a nuisance water-detected alarm. If the probe is not going to be used it should be
disconnected.
3.11 Water Sensing Cable
Some units may be equipped with a water sensing cable. The cable is connected to the terminal
board and ready for installation. Cable lengths will vary depending on the original order and
specifi cations. Typically, the cable is installed around the unit’s perimeter. The cable is supplied
with holding clips. Care should be taken when installing the cable. Be sure the cable is not touching
metal and/or any debris under the raised fl oor.